1. Specification of genset |
Gensets model | KH-64GF |
Rated power | 80KVA/64KW |
Rated Voltage | 400V |
Rated Current | 115.2A |
Rated frequency(HZ) | 50Hz |
Rated Speed | 1500rpm |
Power Factor(COS¢) | 0.8(lagging) |
|
2. Specification of diesel engine |
Engine brand | Perkins |
Engine model | 1104A-44TG2 |
Number of Cylinders | 4 |
Cylinder arrangement | Vertical in-line |
Cycle | Four stroke |
Aspiration | Turbocharged,air to air charge cooled |
Fuel System | Direct injection |
Bore×Stroke (mm×mm) | 105X127 |
Displacement (Liter) | 4.41 |
Compression Ratio | 18.2:1 |
Speed Governor | Electronic |
Cooling System | Forced Water Cooling Cycle |
Total lubrication system capacity (L) | 8 |
Fuel Consumption at 100% Load (L/H) | 14.3 |
Starting Method | DC12V electrical starting |
|
3. Specification of alternator |
Alternator brand | Stamford |
Alternator model | UCI224F |
Number of Phase | 3 |
Connecting Type | 3 Phases and 4 Wires |
Number of Bearing | 1 |
Protection Grade | IP23 |
Altitude | ≤1000m |
Exciter Type | Brushless ,Self-exciting, AVR&100% Copper winding wire |
Insulation Class | H |
Telephone Influence Factor (TIF) | ≤50 |
THF | ≤2% |
Steady State Voltage Regulation | ≤±1% |
Transient State Voltage Regulation | ≤-15%~+20% |