36kv Cable Accessories Cold Shrinkable Indoor Cable Termination

Min.Order: 1
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ 10 ~ 180

Description
36kV cold shrinkable indoor cable termination


Cold Shrink Cable Accessories: 
1. Hifuture cold shrinkable cable accessories adopt world renowned brand liquid/solid silicone rubber material. The products are with excellent insulation, anti-tracking, rebound resistance, heat/cold resistance, ozone resistance, anti-aging, and good dielectric properties, and can be used under various harsh conditions.

2. Geometric stress control method.

3. Standards compliance: IEC60502, GB/T12706.4, EN50180& EN50181(C type bushing)

4. Cold installation, easy and safe without using fire, just by pulling the spiral.


Technical Data:
Rated Voltage8.7/15(17.5)kV12/20(24)kV18/30(36)kV26/35(40.5)kV
Running Temperature17.5kV24kV36kV40.5kV
AC Withstand Voltage and DC Withstand Voltage39kV, 5min or 35kV, 15min, no flashover, no breakdown54kV,5min, or 48kV, 15min, no flashover, no breakdown81kV, 5min, or 72kV, 15min, no flashover, no breakdown117kV, 5min or 104kV, 15 min no flashover, no breakdown
Partial Discharge15kV, PD≤5pC20kV, PD≤5pC30kV, PD≤5pC45kV, PD≤5pC
Impulse Voltage Test95kV, ±10 times125kV, ±10 times170kV, ±10 times200kV, ±10 times
Short Circuit Thermal Stability (Conductor)24kA, 2s twice, no visible damage25kA, 2s twice, no visible damage23kA, 2s twice, no visible damage25kA, 2s twice, no visible damage
Short Circuit Dynamic Stability83kA, not less than 10ms, no visible damage63kA, not less than 10ms, no visible damage83kA, not less than 10ms, no visible damage88kA, not less than 10ms, no visible damage
Constant Voltage Load Cycleapply voltage 1.25U0 to conductor and heat to(90-95)ºC heat for 5h and cool for 3h, total 3 times
Salt Spray Test1.25U0 1000h, no flashover, no breakdown, trip not more than 3 times, no obvious damage
Humidity Test1.25U0 300h, no flashover, no breakdown, trip not more than 3 times, no obvious damage
Long-time Running Temperature-40ºC to 95ºC
Short Circuit Temperature250ºC, lasting time less than 5s
Cable Accessories Conductor Materialcopper, aluminum, copper&aluminum