up to 1-6 Loop Photoelectric Programmable Fire Alarm Monitoring Security System

Min.Order: 1
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ 650 ~ 750

Description

Feature and Benefits

  • Certified EN54-2:1997 +A1:2006, EN54- 4:1997 + A1:2002 + A2:2006
  • LPCB Approved
  • Using advance microprocessor technology with Large memory capacity
  • Enhance user interface combining LCD Touch screen and keypad access
  • Support real time visual algorithm
  • Enhance false alarm prevention
  • Keypad and PC programming
  • Built-in Multiple interface protocol such as USB/Ethernet/CanBus/ Serial/RS485 (Available only in TX7004/4 Panel)
  • Support Loop Powered devices for extra saving on cable cost
  • Built-In Printer and 160 LED Zones Indicators
 

Commissioning Advantage

  • Auto Enrolling of Devices
  • Loop Mapping with colour coding status
  • Monitor device mismatch and dual address conflict
  • Command Builder to create requirements for fire event scenario
  • With Loop protection against power surge
  • One-man test with On/Off sounder Programming Protection

System Capacity

  • 1, 2, 4 loop Panel, (6 loop standalone)
  • Support 254 Devices (1,524 ideal)
  • Network up to 512 Node
  • Programmable Capacity
  • Zones up to 3000
  • Sounders Groups 1-1000
  • Modules Groups 1001- 2000
  • Built-in 160 LED Zones Indicator

Overview

The TX7004 comprise of a range of analogue addressable, microprocessor based fire alarm control equipment to offer flexibility in both design and operation. The System is modular concept for easy tailoring of system design, to meet the full requirements of the project. The TX7004 Intelligent Fire Alarm Control Panel is designed and manufactured to meet the requirement of BS EN54 Part 2&4.
The TX7004 is designed to provide early warning fire detection, to quickly identify the location of fire and provide user definable text informing the occupants of the building of potential smoke spread. Simultaneously, the TX7004 will alert and evacuate the occupants, and control all necessary auxiliary command functions such as elevator control, air handling shut down, gas shut off & damper control, as per the cause and effects requirements configured though Command Builder Set-up.

 

Technical Specification

Listed LPCB / CE-CPR
Certified EN54-2:1997 +A1:2006, EN54-4:1997 + A1:2002 + A2:2006

Power Rating

Input Voltage 240VAC +10%-15%, 50/60Hz
Input Current Consumption 1 A
PSU Output to CIE 24.5 to 28.5 VDC
Batteries 2 x 12V / 24AH

Networking and Interfaces

Panel to panel communication Can Bus [loop] Number of Panels 512
Interface Port USB, RS485 Serial, RS232 Serial, Ethernet

System Capacity

Memory [Non-Volatile] 1000 Fire Events, 10,000 General Event Zones 3,000 programmable
Total Group 3,000 programmable Sounder Group 1,000 programmable
Common Group 2,000 programmable

Loop Specifications

Protocol/Addressing T&A, Value range from 1 to 254
No. of Loop 4 Loop
Protection Built-in 4kV Surge protection
Power rating 16 to 24Vdc
Cabling 1.2Km Max Length/2 x 1.5mm²solid core Fire resistance

Input/outputs

Programmable Relays 4 circuits: Normally Open/Close
Programmable Input 1 Circuit: Power limited 24Vdc (for future use) Programmable Auxiliary Power 19 t0 28 VDC (Note: Current Limited)
Fixed Outputs (FPE/Sounder) 2 Circuits: 18 t0 28 VDC (Note: Current Limited) Indicator 24 LED Status/ 160 Zone Indicators
Display 7" TFT Touch Screen
Keypad 5 Brigade buttons and Programming Keypad
Material / Color Flat sheet Metal / with outer glass door, Orange stripe
Dimension Lx W x H 530 mm x 490 mm x 135 mm
Weight 16.70 Kg
Humidity 0 to 95% Relative Humidity, Non condensing