Description
Application
CYD series miniature circuit breakers are composed of the moulded case, operating mechanism,
contact system, arc-extinguishing system, tripping mechanism, etc. The case is made of the special
plastic high in fire-resistance and strength, so it is very capable of resisting impact and light in weight.
The parts of the operating mechanism employ high strength plastic products in order to assure the
flexible, reliable operation and obtain the minimum moment of inertia as well so that the time from
the moment the short-circuit fault occurs to the operation of the tripping mechanism is very little.
The tripping mechanism is composed of the two part of bimetal sheet overload counter time limit
tripping mechanism and short-circuit instantaneous electromagnetic mechanism. The contact arcextinguishing
system employs the special arc-conducting angle and gangway arc-extinguishing
chamber so it has distinct current limiting characteristics.
Main Technical Data
Standard | | IEC898, GB10963, BS3871.1 |
Number of poles | | 1P, 2P, 3P, 4P |
Rated current(In) | | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 |
Rated voltage(Un) | | AC230/400V |
Rated frequency | | 50/60Hz |
Tripping curve | | B, C, D |
Release action characteristics | Time delay | 1.13In ≥1h non-trip |
1.45In <1h trip |
2.55In 1S <60S trip |
Instantaneous (Curve C) | 5In ≥0.1S non-trip |
10In <0.1 trip |
Magnetic releases operate | | B curve: between 3 and 5In |
| C curve: between 5 and 10In |
| D curve: between 10 and 14In |
Rated breaking capacity(Icn) | | 6000A |
Endurance | | ≥ 2500 |
Circumstance temperature | | -5ºC+40ºC |
Electrical life | | ≥ 6000 times |
Mechanical life | | 20000 times |
Tropical ration | | Treatmen 2(RH95%, at 55ºC) |
Protection degree | | IP20 |