Mqtt Protocol Supported Ethernet Industry 4.0 Controller for Iiot Control PLC Programmable Pr-26DC-Dai-Rt-N

Min.Order: 1
Product origin: Nanjing, Jiangsu, China
Infringement complaint: complaintComplaint
US$ 311.85

Description

About Programming Cable.

Pleased to inform you that our micro plc is developed 100% by ourself ,and they are incompatible with any other brands plc's programming cable. so we strongly suggest you also purchase the programming cable when you purchase the CPU units,we have two types programming cables,one is USB CABLE  (USB communication module PC and ELC units); the other is RS232 CABLE (RS232 programming cable between PC and PR units,or connection cable between  CPU and HMI with standard RS232 port).Without programming cable, you can not set up connection/communication between PC and PLC, further, you naturally can not make programme via PC, and surely unable to download your programme to our PLC.

About Programmable Software.

Programming software For PR Series is xLogicSoft.
Programming software For EXM Series is eSmsConfig.
Download link:https://rievtechplc.en.made-in-china.com

GENERAL SPECIFICATIONS

Timers: 1024
Counters: 1024
Function Blocks: 1024
Operation temp.: -20°C - 55°C
Storage: -40°C - 70°C
Protection: IP20 (Non-waterproof)
RTC accuracy: MAX ±2S/day
RTC Backup at 25 °C: 20 days
Program and settings Backup: 10 years
Data Power-off retentivity: 10 years
Modify parameters via keypad LCD: YES
Dimensions: 133*90*60(Unit:mm)
Certificate: CE
Installation: 35-DIN rail or screw for installation
Expansion capacity: 16 modules (PR-E-16)
Password protection: 4-digit number password protection or disable program upload function
Communication interface: 1 RS232 Port (COM0) & 1 RS485 port (COM1 external) available via optional accessory,                                        2 built-in RS485 (C0M2, C0M3), 1Ethernet port.
Communication protocol: Modbus RTU/ASCII, Modbus TCP
 

Technical Index
 
Power supply:
Nominal voltageDC 24V
Operating limits DC 20.4-28.8V
Immunity from micro power cuts Typ.5 ms
Max. Startup currentMax. 0.3A
Max. absorbed power10W
Protection against polarity inversionsYes
Input parameters:
Input No16 ( I1-IG)
Digital input 16 ( I1-IG)
Analogue input 8 ( I1-I8)(0..10V DC) +4(ID-IG)(0...20mA OR 0..10V DC)
Digital input and analog inputs (0...10V)10bits( I1-I8 )
Inputs used as digital inputs( I1-I8 )
Input voltage DC0-28.8V
Input signal0 < 5V DC;<0.08mA
Input signal1 > 8 V DC;>0.12mA
Input current 0.16mA @ 10.8V dc
0.18mA @ 12.0 V dc
0.34mA @ 24 V dc
0.41mA @ 28.8 V dc
Response time 0 to 1 :Typ. 10.5 ms ;1 to 0 :Typ. 1.5 ms
Maximum counting frequencyTyp.:4 HZ
Sensor typeContact or 3-wire PNP
Input typeResistive
Isolation between power supply and inputsNone
Isolation between inputsNone
Inputs used as analog inputs(0..10V)( I1-I8 )
Measurement rangeDC 0---10V
Input impedanceMin, 24KΩ; Max. 72KΩ
Input voltage28.8 V DC max
Resolution10bit ,0.01V
Accuracy at 25 °C± (Max.0.02)V
Accuracy at 55 °C± (Max.0.04)V
Isolation between analog channel and power supplyNone
Cable length10 m max. shielded and twisted
Digital and high speed inputs(I9--IC)
Digital inputs( I9-IC ) 
Input voltage DC0-28.8V
Input signal0 < 5V DC; <1mA
Input signal1 > 8 V DC;>1.6mA
Input current2.1mA @ 10.8V dc
2.3mA @ 12.0 V dc
4.6 mA @ 24 V dc
5.5 mA @ 28.8 V dc
Response time 0 to 1 :<1 ms ;1 to 0 :<1 ms
High speed inputs( I9-IC ) 
Maximum counting frequency60kHZ(I9--IC)
Digital and analog(0--10V)&analog(0...20mA)(ID-IG)
Inputs used as digital inputs( ID-IG )
Input voltage DC0-28.8V
Input signal0 < 5V DC;<0.08mA
Input signal1 > 8 V DC;>0.12mA
Input current 0.16mA @ 10.8V dc
0.18mA @ 12.0 V dc
0.34mA @ 24 V dc
0.41mA @ 28.8 V dc
Response time 0 to 1 :Typ. 10.5 ms ;1 to 0 :Typ. 1.5 ms
Maximum counting frequencyTyp.:4 HZ
Sensor typeContact or 3-wire PNP
Input typeResistive
Isolation between power supply and inputsNone
Isolation between inputsNone
Inputs used as analog inputs(0..10V)( ID-IG )
Measurement rangeDC 0---10V
Input impedanceMin, 24KΩ; Max. 72KΩ
Input voltage28.8 V DC max
Resolution10bit ,0.01V
Accuracy at 25 °C± (Max.0.02)V
Accuracy at 55 °C± (Max.0.04)V
Isolation between analog channel and power supplyNone
Cable length10 m max. shielded and twisted
Input signal0 < 5V DC;<0.08mA
Input signal1 > 8 V DC;>0.12mA
Input current0.16mA @ 10.8V dc
0.18mA @ 12.0 V dc
0.34mA @ 24 V dc
0.41mA @ 28.8 V dc
Response time 0 to 1 :Typ. 10.5 ms ;1 to 0 :Typ. 1.5 ms
Sensor typeContact or 3-wire PNP
Input typeResistive
Isolation between power supply and inputsNone
Isolation between inputsNone
Inputs used as analog inputs(0..20mA)( ID-IG )
Analogue signal0/4….20mA current
Input impedance260Ω
Resolution0.02mA
Accuracy at 25 °C0.05mA
Cycle time for analog value generationTyp. 50 ms
Protection against polarity inversionsyes
Overvoltage protectionYes, if the input voltage is >6.5V, this one is automatically switched on 0--10V configuration
Isolation between power supply and inputsNo
Cable length<=30M with shielded twisted cable(sensor not isolated)
  
Output
Digital/Transistor output(PNP) - Q1,Q2
Breaking voltageDC 5--30V
Nominal voltage ≤ Supply voltage
Nominal currentMax. 0.3 A per channel
Max. breaking current0.65 A
Voltage drop< 2 V   for I = 0.3 A (at state 1)
Response timeMake ≤ 1 ms
Release ≤ 1 ms
Frequency (Hz)resistive load : 10 Hz  
inductive load : 0.5 Hz
Built-in protectionsAgainst overloads and short-circuits: No
Against overvoltages (*): No
Galvanic isolationNone
PWM frequency10K HZ
PWM cyclic ratio0  to 100 %
PWM accuracy at 120Hz< 0.5 % (20 % -80 %) load at 10 mA
Max. Breaking current PWM50 mA
Max. cable length PWM20m
5A Relay 4 outputs from Q3 to Q6
Max. breaking voltage CE:AC 250 V/DC 30 V 5A
UL:AC 250 V/DC 30 V 3A
Electrical durability Expectancy105 Operations at Rated Resistive Load
Mechanical life107 Operations at No Load condition
Response timeOperate Time: 15 mSec. Max.
Release Time: 10 mSec. Max.
Built-in protectionsAgainst short-circuits: None
Against overvoltages and overloads: None
10A Relay 4 outputs from Q7 to QA
Max. breaking voltage CE:AC 250 V/DC 30 V 10A
UL:AC 250 V/DC 28 V 5A
Max. Allowable Power Force1250VA
Electrical durability Expectancy105 Operations at Rated Resistive Load
Mechanical life107 Operations at No Load condition
Response timeOperate Time: 15 mSec. Max.
Release Time: 10 mSec. Max.
Built-in protectionsAgainst short-circuits: None
Against overvoltages and overloads: None
Communication ports parameters:
COM0_TTL portCan be used as program port with PR-RS232&PR-USB;
Also can be convert to RS232 port with PR-RS232
Can be convert to RS485 port with PRO-RS485
Note:Need move away the expand cover to use it
Can be used as modbus master or slave
Built-in RS485 COM21 built-in RS485 port (Terminal A+,B-)
Can be used as modbus master or slave
Built-in RS485 COM31 built-in RS485 port (Terminal A+,B-)
Can be used as modbus master or slave
Ext RS485 COM1Need use with PR-E-RS485 module
Can be used as modbus master or slave
Ethernet port: Built-In(10M/100M),
1.Can be used as program or communication
2.Can be used as modbus master or slave
Monitoring webserver pageYes
Xlogic<--->Xlogic(by Ethernet)1 xlogic works as tcp server can connect with 8 tcp client   xlogics or other tcp devices.
Xlogic<--->Ethernet/Internet:1 xlogic works as TCP clients can connect with 8 different tcp servers separately in maximum
Other parameter
WeightApprox.400g

Dimension








 

Product Tag:
Related categories:
Scroll to Top