Sorotec HP9116c/HP9316c Plus 1-20k Series 3 Phase High Frequency Online UPS

Min.Order: 5
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ 200

Description

SOROTEC HP9116C/HP9316C PLUS 1-20K Series 3 Phase High Frequency Online UPS

Typical application

Data centre, bank station, network , communication equipment, office, automatic equipment,

monitor equipment, control system

Highly flexible and extendable

Battery can choose

1.Battery voltage can be choice depend on capacity , can satisfy different requirement.

2.Convenience to get more back up time and lower system invests

3.Convenience to save cost of battery

4.Intelligent battery monitors Charge current can be adjust

5.Standant charge current 4A

6.Support more discharge time and more capacity battery for 8A charger Input topology design

7.Support three phase input or single phase input for three phase UPS

8.Super wide input voltage and frequency range suitable for bad power electirc environment

9.Digital control DSP technology and best power component make the system safe and reliable

 

 

Multifunction friendly design

Advanced parallel technology

1.Stable parallel control technology make sure current sharing to 1%

2.Select trip technology can avoid and isolation system fault then improved system availability

3.Flexible extension capacity and redundance management that can satisfy all kinds of requirements

4.Support maximum 3 units for parallel working Flexible strategy

5.On line mode provides higher system availability

6.High efficiency mode provides more economic operation

7.Frequency conversion provides more stable output

 

Higher function

Output power factor up to 0.9

1.Output power factor is 0.9 that mean can take more load, if you take same load that can get higher reliability.Input power factors up to 0.99

2.Three phase input model support three phase PFC , input THDI<5%

3.Output voltage regulation 1%, frequency regulation 0.1%, parallel current sharing 1%.

The efficiency up to 94%

4.Efficiency up to 93.5%when take the 30%load

5.ECO mode efficiency up to 98%

 

Technical Parameters

ModelHP9116C/HP9316C 10-20KVA PLUS
10KT-XL15KT-XL20KT-XL
Rated Power10KVA/9KW15KVA/13.5KW20KVA/18KW
Rated Voltage220VAC/380VAC 3phase with ground
Rated Frequency40-70 Hz (50/60 Auto-sense)
Input
Voltage RangeSingle phase: 120 ~ 275VAC ( 176-275VAC full load ) Three phase: 209-475VAC ( 304-475VAC full load)
Power Factor>0.95(Three phase)≥0.99
Output
Voltage Regulation208/220/230/240VAC (±1%)
Frequency Regulation50/60HZ±0.05 Hz
Power Factor0.9
Voltage DistortionLinear load<2% ,Non-Linear load<5%
Overload Capability105% ~ 125% for 10min; 125% ~ 150% for 30s,>150% for 500 ms
Current Crest Ratio3:01
Transfer Time0ms (AC mode→Battery mode)
Battery
DC Voltage192VDC192/216V/240VDC
Recharge Current4A4A (8A optional)
Display
LCDDisplay input/output Voltage, Frequency, Battery voltag, Battery capacity, Loading rate.
Communication
InterfaceSmart RS232,SNMP card (optional) USB (optional)
Environment
Operation Temperature0~40ºC
Humidity0~95% (Non-condensing)
Storage Temperature-25ºC~55ºC
Sea Level Elevation<1500m
Noise Level (1m)<55dB
Physics Characteristic
Weight(KG)16.931
Dimensions :(Wx D x H)mm212X420X500248X565X500