11kv/15kv/27kv/38kv 50Hz/60Hz Pole Mounted Vacuum Circuir Breaker for Recloser

Min.Order: 1
Product origin: Ningbo, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 3000

Description
No.ItemUnitData for ZW32-12KVData for ZW32-15KV
1Rated VoltageKV1215
2Rated insulation level
(phase to ground, phase to phase)
1 min Frequency withstand voltageDryKV4250
Wet3445
Lighting Impulse Withstand Voltage(Peak)KV75110
3Medium Interruption:Vacuum
4Medium isolation: Solid polymer
5Mechanism of operation (closing and shot): Magnetic
6Assembly: Suitable weather for substation
7Environmental operating temperature: FROM -40ºC-+50ºC
8Position indicator: Green-closed; Open-red
9Minimum distance of contouring of the insulationMM400600
10Rated FrequencyHz50/60
11Rated CurrentA630/800/1250
12Rated Min Start-up CurrentNumericalAadjustable
Permissible deviation%±10
13Rated Fault Interrupter CapacityKA/3s12.5/20
14Rated Fault Symmetrical Making CurrentKA12.5/20
15Rated Short-Time Withstand CurrentKA12.5/20
16Rated Peak Withstand CurrentKA12.5/20
17Interrupting Time(Max) (Cycle)sNo more than 4
18The conditions of different phase earthed fault short-circuit breaking currentKA17.3
19Rated Cable Charging Breaking currentA25
20Rated Operating Sequence O-0.1s-CO-2s-CO-2s-CO-C
21Rated Operation VoltageVAC/DC110/125/220/240
22Rated Short-Circuit Current Breaking TimesTime 
90%~100% Rated Short-Circuit Current volume16
45%~55% Rated Short-Circuit Current volume44
15%~20% Rated Short-Circuit Current volume56
23Mechanical Life (Mechanical stability)Time/Unit Operation15000
24Current TransformerPrimary Rated CurrentA200/400/600/1000
Secondary Rated Current1A or 5A
Accuracy ClassCL0.2/5P20
CapacityVA2VA TO 15VA
Installation Built in /In bushing
25Capacitor Voltage TransformerPrimary Rated VoltageKV12/3/15/√3
Secondary Rated VoltageV0.4-7
Accuracy Class%1%
Installation Outdoor/In busing
26Special Manual Closing Mechanism 
 
optional
27Earthing Solidly Earthed
 
No.
ItemUnitData for ZW32-27KVData for ZW32-38KV
1Rated VoltageKV2738
2Rated insulation level (phase to ground, phase to phase)1 min Frequency withstand voltageDryKV6595
Wet5080
Lighting Impulse Withstand Voltage(Peak)KV145/150185
3Medium Interruption:Vacuum
4Medium isolation: Solid polymer
5Mechanism of operation (closing and shot): Magnetic
6Assembly: Suitable outdoor for substation or pole mounted
7Environmental operating temperature: FROM -40ºC-+50ºC
8Position indicator: Green-closed; Open-red
9Minimum distance of contouring of the insulationMM680900
10Rated FrequencyHz50/60
11Rated CurrentA200A/400A/630A/1250A
12Rated Min Start-up CurrentNumericalAAdjustable
Permissible deviation%±10
13Rated Fault Interrupting CapacityKA/3S12.5/20
14Rated Symmetrical Making CurrentKA12.5/20
15Rated Short-Time Withstand CurrentKA12.5/20
16Rated Peak Withstand CurrentKA12.5/20
17Interrupting time(Max)(Cycle)SNot more than 4
 18The conditions of different phase earthed fault short-circuit breaking currentKA12.520
19Rated Cable Charging Breaking currentA25
20Rated Operating Sequence O-0.1s-CO-2s-CO-5s-CO-C
21Rated Operation VoltageVAC/DC110/125/220/240
22Rated Short-Circuit Current Breaking TimesTime 
 90%~100% Rated Short-Circuit Current volume 16
 45%~55% Rated Short-Circuit Current volume 44
 15%~20% Rated Short-Circuit Current volume 56
23Mechanical Life (Mechanical stability)Time/unit Operation10000
24Current TransformerPrimary Rated CurrentA200/400/600/1000
Secondary Rated CurrentA1A or 5A
Accuracy ClassCL0.25/5P20
CapabilityVA2VA TO 15VA
Installation Built in /In bushing
25Capacitor Voltage TransformerPrimary Rated VoltageKV27/3/38/3
Secondary Rated VoltageV0.4-7
Accuracy Class%1%
Installation Outdoor/In busing
26Special Manual Closing Mechanism Option
27Farthing Solidly Earthed