Frequency Conversion Provides More Stable Output UPS HP9116c Plus 3kVA

Min.Order: 5
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ 1000 ~ 10000

Description

Frequency Conversion Provides more Stable Output UPS HP9116C PLUS 3KVA

HP9116C /HP9316C 1-20KVA (1Ph in/1 Ph out& 3Ph in/1 Ph out) PLUS  Series High Frequency Online UPS
Model :1kva-20kva
Nominal Voltage :220/230/240/380vac
Nominal Frequency:40-70hz
Output Power Factor :0.9
Parallel Working: Maximum 3PCS UPS

Application:
Data Center ,Bank Station,Network,Communication Equipment,Office,Automatic Equipment,
Monitor Equipment,Control System.


Muilti-function and Friendly Design
Advanced Parallel Technology

Stable parallel control technology make sure current sharing to 1%.

Select trip technology can avoid and isolation system fault then improved system availability.

Flexible extension capacity and redundance management that can satisfy all kinds of requirements.

Support maximum 3 units for parallel working Flexible strategy.
Flexible Strategy
On line mode provides higher system availability.

High efficiency mode provides more economic operation.

Frequency conversion provides more stable output.

 

More Flexible and  Powerful  Extendable Capacity
Battery Type Can Be Choice
1.Battery voltage can be choice depend on capacity , can satisfy different requirement.

2.Convenience to get more back up time and lower system invests.

3.Convenience to save cost of battery.

4.Intelligent battery monitors Charge current can be adjust.
Charge Current Can Be Adjust
Standant charge current 4A.

Support more discharge time and more capacity battery for 8A charger Input topology design.
Input Technology Design
1.Support three phase input or single phase input for three phase UPS

2.Super wide input voltage and frequency range suitable for bad power electirc environment

3.Digital control DSP technology and best power component make the system safe and reliable


Higher Power Factor /Higher Efficiency /Support Three Phase Input
Output Power Factor Up To 0.9

Output power factor is 0.9 that mean can take more load, if you take same load that can get higher reliability.
Input power factors up to 0.99

Three phase input model support three phase PFC , input THDI<5%

Output voltage regulation 1%, frequency regulation 0.1%, parallel current sharing 1%.

The efficiency up to 94%

Efficiency up to 93.5%when take the 30%load

ECO mode efficiency up to 98%

Technical Specifications:

ModelHP9116C/HP9316C 10-20KVA PLUS
10KT-XL15KT-XL20KT-XL
Rated Power10KVA/9KW15KVA/13.5KW20KVA/18KW
Rated Voltage220VAC/380VAC 3phase with ground
Rated Frequency40-70 Hz (50/60 Auto-sense)
Input
Voltage RangeSingle phase: 120 ~ 275VAC ( 176-275VAC full load ) Three phase: 209-475VAC ( 304-475VAC full load)
Power Factor>0.95(Three phase)≥0.99
Output
Voltage Regulation208/220/230/240VAC (±1%)
Frequency Regulation50/60HZ±0.05 Hz
Power Factor0.9
Voltage DistortionLinear load<2% ,Non-Linear load<5%
Overload Capability105% ~ 125% for 10min; 125% ~ 150% for 30s,>150% for 500 ms
Current Crest Ratio3:01
Transfer Time0ms (AC mode→Battery mode)
Battery
DC Voltage192VDC192/216V/240VDC
Recharge Current4A4A (8A optional)
Display
LCDDisplay input/output Voltage, Frequency, Battery voltag, Battery capacity, Loading rate.
Communication
InterfaceSmart RS232,SNMP card (optional) USB (optional)
Environment
Operation Temperature0~40ºC
Humidity0~95% (Non-condensing)
Storage Temperature-25ºC~55ºC
Sea Level Elevation<1500m
Noise Level (1m)<55dB
Physics Characteristic
Weight(KG)16.931
Dimensions :(Wx D x H)mm212X420X500248X565X500

 



Packaging & Shipping

Company Profile


Shenzhen SORO Electronics Co., Ltd is a professional UPS and inverter manufacturer in the field of power electronics for 13 years. We have two large production UPS sites, Zhejiang and Shenzhen. We have own our SMT department. SORO UPS has been a leading enterprise in the UPS industry in China.

Since established, The company has carried out three strategies: operation innovation strategy, people-oriented strategy , technical guidance strategy, and implemented strict scientific management with full-fledged quality management system. The company invests 10% of its annual revenue in researching and development every year. We had international advanced equipments for developing , testing and producing. SORO UPS invited the best technical elites at home, meanwhile, the company established perfect cooperation relationship with domestic scientific research units and academies, to strive for making products that reach advanced world standards. 

Certifications

1,QC Control

The company ranks first in passing the ISO9001 international quality system certification.We established a complete quality system ranging from material source, process, assembling to testing. Most of our products have been certified to meet international safety standards, such as CE (LVD/EMC), CUL,FCC. 

2,Best Partner

We have co-operative partner throughout the world including USA, Europe, South America, South Africa, Middle Eastern, India, Turkey, Pakistan, Iran and so on .We offer wide range quality products either from our own standard range or customer-made to your specifications. SORO is becoming the most growthful China UPS supplier all over the world. 

FAQ

1.How to choose suitable inverter?
If your load is resistive loads, such as: bulbs, you can choose a modified wave inverter. But if it is inductive loads and capacitive loads, we recommend using pure sine wave power inverter.
For example: fans, precision instruments, air conditioner, fridge, coffee machine, computer, and so on.
Modified wave can be started with some inductive loads, but effect for load using life,because capacitive loads and inductive loads need high quality power.

2.How do I choose the size of the inverter?
Different types of load demand for power are different. You can view the load power values to determine the size of the power inverter.
Notice:
Resistive load: you can choose the same power as the load. 
Capacitive loads: according to the load, you can choose 2-5 times power.
Inductive loads: according to the load, you can choose 4-7 times power.

3.How connection between batteries and an power inverter?
We usually believe that cables connecting battery terminal to inverter shorter is better. If you are just standard cable should be less than 0.5M, but should correspond to the polarity of the batteries and inverter-side outside. If you want to lengthen the distance between battery and inverter, please contact us and we will calculate the recommended cable size and length. Due to long distances using a cable connection, there will be a reduced voltage, which means that the inverter voltage would be far below the battery terminal voltage, this inverter will appear under voltage alarm conditions.

4.How to calculate the load of working hours requires configuration of the battery size?
We will usually have a formula to calculate, but it is not hundred percent accurate, because there is also the battery's condition, the old batteries have some loss,so this is only a reference value:
Work hours = battery capacity * battery voltage * 0.8/load power (H= AH*V*0.8/W)