Motorized Operation Mechanism 500nm for 72.5kv/145kv Disconnector /Circuit Breaker

Min.Order: 10
Product origin: Ningbo, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 1000

Description




 
 THE BIDDER INFORMATION
1. Name of offeror companyNINGBO HYUAN POWER INDUSTRY CO.,LTD
2. Name FactoryNINGBO HYUAN POWER INDUSTRY CO.,LTD
3. Country of Origin FactoryCHINA
4. Name of contact personTAILICHEN
5. Contact phone008613805895904
6. Contact Email[email protected]
Technical data         Unity                SpecificationofferedObservations
1) Technical data
1.1Brand (*)HEMG 
1.2Model (*)CJ 
1.3rated torque: 500NMRequired500 
1.4Operating frequency: 60HzRequired60 
1.5Operating Voltage: 125 ± 10%vdcRequired125VDC+/-10% 
1.6Type of operation    
            1.6.1 Electric RequiredELECTRIC  
            1.6.2 Manual crank RequiredMANUAL CRANK 
1.7keypads    
             1.7.1 Opening: Green Color RequiredGREEN COLOR 
             1.7.2 Close: Color Red RequiredRED COLOR 
1.8Wiring contact closing and opening available in borneras RequiredYES 
1.9Position selector    
            1.9.1 Local RequiredLOCAL 
            1.9.2 Remote RequiredREMOTE 
            1.9.3 Maintenance RequiredMAINTENANCE 
1.10Motor Voltage: 125Vdc / VacRequired125VDC 
            1.10.1 Operating voltage range:         vdc80 to 15080-150 
1.11Control coils 125vdcRequired125VDC 
            1.11.1 Operating voltage range:         vdc 80 to 15080-150 
1.12Limit (Limit Swich) Adjustable: Degrees90 and 18090/180 
1.13Direction of rotation for opening: Schedule  RequiredANTICLOCKWISE  
1.14Breaker protection shot Auxiliary Contact  RequiredYES 
1.15Heating Required  
            1.16.1 Heating Voltage: 120VacRequired120VAC 
            1.16.2 Adjustable Temperature:° C30;55≥30;≤55 
1.17contacts    
            1.17.1 normally open contact 10c / uRequired10 
            1.17.2 Contact normally closed 10c / uRequired10 
1.18Block wiring contacts available on terminal blocks RequiredYEW 
1.19Lamp for indoor lighting    
             1.19.1 Lamp type: LED RequiredYES 
             1.19.2 Lamp power        W(*)10W 
1.20The lower cap must be removable and smooth. RequiredYES 
1.21Set in block control terminals, power and signaling RequiredYES 
1.22Landing site Required  
             1.22.1 Landing Holes: 2c / uRequired2 
1.23 DC Contactor: 2c / uRequired2 
             1.23.1 force contacts NA: 4c / uRequired4 
             1.23.2 auxiliary contacts NC: 2c / uRequired2 
             1.23.3 auxiliary contacts: 2c / uRequired2 
1.24Lock system    
            1.24.1 Lockout RequiredYES 
            1.24.2 Mechanical lock RequiredYES 
1.25Degree of protection: IP55 RequiredIP55 
1.26Manufacturing material: aluminum or stainless steel Required  
1.27Fixing brackets 4 5/8 holes in galvanized steel bar RequiredSTAINLESS STEEL 
1.28Disconnector opening time:Sec.≤9<=9 
1.29Construction standards: IEC 62271-102, 62271-1 RequiredIEC62271-102,IEC62271-1 
1.30Or latchkey lock: Handle with possibility to type padlocked RequiredYES 
1.31Control planes:  RequiredYES 
2) testing and factory testing
2.1IEC 62271-1, 60255-5 and 62271-102 a) Insulation Resistance Motor b) opening and closing speed c) Rotation d) electrical and mechanical lock e) Test torque RequiredYES 
 
 
 
 
 