ASME Sec I Standard High Performance Steam Safety Valve (GA 901 / 902 / 911 / 912)

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 1

Description

ASME Sec I Standard High Performance Steam Safety Valve (GA 901 / 902 / 911 / 912)

Product Description
Application

Application:

DIN 901 / 902 Spring Loaded Full Lift Safety Valve  is applicable as the pressure protecting device in the equipment or pipelines for steam, air,etc.,  which the working medium is  ≤350ºC.

Product Features

DIN Standard Safety Valve Features: 

Safety valves were first used on steam boilers during the industrial revolution. Early boilers without them were prone to accidental Explosion.
Safety valves also evolved to protect equipment such as pressure vessel (fired or not) and heat exchangers. Safety valve term should be limited to compressible fluid application (gas, vapor, steam).

The two general types of protection encountered in industry are thermal protection and flow protection.

 For liquid-packed vessels, thermal relief valves are generally characterized by the relatively small size of the safety valve necessary to provide protection from excess pressure caused by thermal expansion. In this case a small valve is adequate because most liquids are nearly incompressible, and so a relatively small amount of fluid discharged through the relief valve will produce a substantial reduction in pressure. 

Specification

DIN Standard Safety Valve Specification

Type

Nominal Pressure

Body Material

Nominal Diameter

Working Temp.

901/902/911/912

PN40/16

1.0619+N

DN20/32-DN150/250

-10C~450C

901/911

PN40/16

1.4408

DN20/32-DN100/150

-60C~400C

Product Parameters

DN

20/32

25/40

32/50

40/65

50/80

65/100

80/125

100/150

120/200/

150/250

Throat Diameter do

(mm) 

18

22

29

36

45

58

72

80

100

125

Orifice Area Ao(mm)

254

398

661

1018

1590

2688

4072

6362

8825

12266

Weight (Kg)

8.5

10

14

20

28

40

53

80

125

165

A full lift safety valve is one in which the disc lifts sufficiently, so that the curtain area no longer influences the discharge area. The discharge area, and therefore the capacity of the valve are subsequently determined by the bore area. This occurs when the disc lifts a distance of at least a quarter of the bore diameter. A full lift conventional safety valve is often the best choice for general steam applications.

Full lift safety valve opening height is more than one fourth times of the flow diameter. it has an advantage of discharging greatly .

View of the factory
 
Product Tag:
Related categories:
Scroll to Top