No. | Item | Unit | Data | ||
1. | Rated voltage | KV | 12/24/36/40.5 | ||
2. | Power frequency | Wet | 42/65/70/95 | ||
dry | 45/70/80/110 | ||||
3. | Lingthning impluse withstand voltage(peak value) | 75/95/125/150/170/185/200 | |||
4. | Rated current | A | 630/1250A/1600/2000/2500A | ||
5. | Rated short circuit breaking current | KA | 25/31.5/40 | ||
6. | Rated capacitor bank breaking current | A | 600/800 | ||
7. | Rated short circuit breaking times | Times | 30 | ||
8. | Rated making current | KA | 63/80/100 | ||
9. | Rated short circuit peak withsatnd current | ||||
10. | Rated shortcircuit withstand curren | 25/31.5/40 | |||
11. | Rated short time duration time | S | 3/4 | ||
12. | Complete breaking time | ms | ≤100 | ||
13. | Opening time | Highest operate voltage | 15~50 | ||
Rated operate voltage | 15~50 | ||||
Lowest operate voltage | 30~60 | ||||
14. | Closing time | 25~50 | |||
15. | Contact closing bounce time | ≤3 | |||
Out of simultaneity of contact switching | ≤2 | ||||
Contact overitravel on Opening | mm | ≤2 | |||
16. | Mechanical life | 20000(Normal) | |||
17. | Electrical life(Rated onload switching) | 10000(Noraml) | |||
18. | Rated operate sequence | O-0.3-CO-180S-CO | |||
19. | Weight | ≤250kg |