3 Phase Load Bank 1000kw Load Bank Unit for Generator Test Testing

Min.Order: 1
Product origin: Shijiazhuang, Hebei, China
Infringement complaint: complaintComplaint
US$ -1

Description
3 Phase Load Bank 1000kw Load Bank Unit for generator test testing
Introduction

(1) According to the special requirements of users on site, in the agreement the technical standards of AC400-1000kW Automatic Load Bank (hereinafter referred to as "system") and its accessories are proposed including their function, performance, usage, structure, installation and test to provide users with a high efficient and reliable choice, in order to meet the need for generator load test.
(2) The system consists of 1 sets of 1000kW Resistive load bank. The System is made up of two parts of measurement and control and load, mainly including AC dry load, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, PC software and so on.

(3)This system, which is of independent research and development of electricity load test equipment by our technology, combining dry load module with the automatic measurement and control module, can accurately detect all kinds of generator output power and load capacity, full load and overload test.
The system can be used with a computer to realize the intelligent control, automatically completing the special test to all electrical parameters of generating set and generating tables, graphs, and supporting the print, comprehensively from the cumbersome manual operation to provide scientific and efficient detection means for the power generating sets.
(4) All the schematic diagrams of this agreement are for reference only please in kind prevail 
AC400-1000kW Automatic Load Bank
Rating Voltage/Frequency400VAC, 3 phase 4 wire, wire voltage 400V, phase voltage 230V
50Hz
Rated Load PowerResistive load: 1000kW
Installed CapacityResistive load: 1000kW
Load Step1,2,2,5,10,10,20,50,100,200,200,200,200kW, min step load: 1kW
PF(Power Factor)1
Load Tolerance  (each step)±5%
Load Tolerance(overall)±3%
Display Precision0.5 class
Control PowerExternal 380VAC/50Hz, 3 phase 4 wire, 220V 1-phase
Wire ConnectionLoad power supply input--Copper bar 
Control power supply input--Connector-bar
InsulationF
Duty CycleContinuous  
Cooling TypeForce air cooling, horizontal air inlet and horizontal air outlet
TransportationHoisting, there are lifting lug on top and castors at the bottom of casing
Dimension  About 2440mm*1400mm*1680mm(L×W×H)
Weight About 1500kgs
Casing ColorGrey(RAL7035)or as required
Operating Environment Parameter
WorkplaceIndoor or outdoor 
Ambient Temperature-20ºC~+50ºC
Relative Humidity≤95%
Altitude≤2500 meter
Atmospheric Pressure86~106kPa
Brands of Main Components
ContactorSchneider
FuseMiro
PLCSiemens
Data processing softwareKaixiang(self-developed)
Alloy ResistanceKaixiang(self-developed)





4.Why choosing us
The earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.
The most patent technology and scientific research awards gainer in China.
Advanced detection method and strict inspection procedure build the qualified quality.
Customized production meet the individual requirement.
Prompt delivery & excellent after sales service.
Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.
5.Contact Information


Scroll to Top