Tangent Delta Meter in Transformers Power Factor Meter Tan Delta Tester



 

Product Description

 

Tan Delta (TD) - also referred to as Dissipation Factor or sometime even Power Factor - is an excellent diagnostic test that provides an indication as to the quality of the dielectric insulation used in electrical apparatus. By analyzing the dielectric losses in theinsulation, the GDGS Series of Tan Delta test instruments provide the testing engineer with a versatile high voltage diagnostic system that is suitable for testing MV cable such as XLPE, EPR, PE and PILC. In addition, other electrical apparatus such as capacitors, transformers and large rotating machines can also be diagnosed.

 

Product Features

 

GDGS Automatic 10KV Tan Delta & Dissipation Factor Tester is used to measure dissipation factor (PF) in heavy interference site such as power plants or power substations. It can also be used in laboratory for high accurate test.

The Tan Delta tester is whole in one designed: including precision digital bridge, power unit, reference capacitor (CN), step-up transformer and other electronic circuits. It's also using frequency shift technology, FFT (Fast Fourier Transform algorithm) and digital filtering. When started, it's running automatically and then outputs the results on LCD display and prints the results automatically.

 

Product Parameters

 

Measurement RangeCapacitance value: 3pF ~ 60000 pF/10kV 60pF ~ 1μF/0.5kV
Dissipation range: 0 ~ 100% unlimited, resolution: 0.001%,
 The Automatic identification of capacitance,
inductance, resistance test products
Maximum error
 
Capacitance accuracy: ± (1.0% × reading ± 1 pF)
Dissipation accuracy: ± (1.0% × reading ± 0.04%)
Resolution
 
Capacitance resolution: min. 0.001 pF
Resolution of dielectric loss: minimum resolution 0.001
Test current range10μA~5A
Internal high voltageSetting voltage range: 0.5 to 10kV,
maximum output current: 200mA
Test frequency 50Hz single frequency, 45/55Hz automatic double frequency conversion
Power supply180V ~ 270VAC ,50Hz / 60Hz ± 1%
Operating temperatureambient temperature: 0 ~ 40 ºC;
ambient humidity: ≤ 90% RH, no condensation
Size and weight550*490*580mm,28kg

 