DZ30LE Residual Current Operated circuit-Breaker with Overcurrent Protection
Sandard | IEC/EN61009 | ||
Electrical features | Type(wave form of the earth leakage sensed) | Electro-magnetic type, electronic type | |
Rated current In | A | A,AC | |
Poles | P | 1P+N | |
Rated voltage | V | AC 240/415 | |
Rated Current : | 10,16,20,25,32,40A | ||
Rated sensitivity I△n | A | 0.01,0.03,0.1,0.3,0.5 | |
Insulation voltage Ui | V | 500 | |
Rated residual making and breaking capacity I△m | A | 630 | |
Short-circuit current I△c | A | 3000, 4500, 6000 | |
SCPD fuse | A |
| |
Rated frequency | Hz | 50/60 | |
Pollution degree | 2 | ||
Mechanical features | Electrical life | t | 4000 |
Mechanical life | t | 10000 | |
Protection degree | IP20 | ||
Ambient temperature (with daily average ≤35ºC) | ºC | -25~+40 | |
Storage temperature | ºC | -25~+70 | |
Installation | Terminal connection type | Cable/U-type busbar/pin-type busbar | |
Terminal size top/bottom for cable | mm2 | 25 | |
AWG | 18-3 | ||
Terminal size top/bottom for busbar | mm2 | 25 | |
AWG | 18-3 | ||
Tightening torque | N*m | 2.5 | |
In-lbs | 22 | ||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip device | ||
Connection | From top and bottom |
Breaker | RCBO DZ32LE | |||||||||
Number of poles | 1P+N | |||||||||
Rated current in | A 10 16 25 32 40 | |||||||||
Rated frequency | Hz 50 | |||||||||
Rated operating voltagge Ue | V 230,400 | |||||||||
Rated insulation voltage Ui | V 500 | |||||||||
Rated short circuit breaking capacity Im | A 630 | |||||||||
Rated limited short circuit current Inc | A 6000 | |||||||||
Rated residual action current I△n | mA 30 100 300 | |||||||||
Anti~interference level | 0.5 цs/100kHz,200A peak value | |||||||||
8/20цs, 3000A peak valye | ||||||||||
Mechanical life | times 10000 | |||||||||
Protection level | lp20 | |||||||||
Product type | Type A, Type AC,Type S | |||||||||
Installation mode | Din rail plug~in | |||||||||
Connection mode | Terminal with clip | |||||||||
Ambient air temperature | Min/Max ºC -25/+40 | |||||||||
Altitude | Max m 2000 | |||||||||
Leading wire | Terminal busbar method Min/Max mm 1/35 | |||||||||
Screw torque | N · m 2 2.5 | |||||||||
Outline dimensions (length X width X height) | 2P mm 90×36×76 | |||||||||
Weight | 2P kg 0.275 | |||||||||
Our Advantages