Technical Data | |||||||
Genset Model | Prime Power (KW/KVA) | Engine Model | Clylinders | Bore×Stroke (mm) | Gas Consumption Rate (m3/kw.h) | Displacement (L) | |
KW | KVA | ||||||
NG2-30KW | 30 | 37.5 | 1004NG | 4 | 100×127 | 0.5-0.3 | 3.99 |
NG2-40KW | 40 | 50 | 1006NG | 6 | 100×127 | 0.5-0.3 | 5.98 |
NG2-90KW | 90 | 112.5 | 1006-G6TAG | 6 | 100×127 | 0.5-0.3 | 5.98 |
NG2-100KW | 100 | 110 | R615 | 6 | 126×130 | 0.5-0.3 | 9.7 |
NG2-120KW | 120 | 132 | R615 | 6 | 126×130 | 0.5-0.3 | 9.7 |
NG2-150KW | 150 | 165 | R618 | 6 | 126×150 | 0.5-0.3 | 11.2 |
NG2-160KW | 160 | 200 | D11 | 6 | 128×142 | 0.5-0.3 | 10.96 |
NG2-220KW | 220 | 275 | D15 | 8 | 128×142 | 0.5-0.3 | 14.62 |
NG2-320KW | 320 | 400 | D22 | 12 | 128×142 | 0.5-0.3 | 21.93 |
NG2-440KW | 440 | 500 | D30 | 16 | 128×142 | 0.5-0.3 | 29.24 |
ACCEPTABLE WORKING CONDITIONS: | |
Ambient temperature : | -40°C~+45°C |
(antifreeze or hot water needed for below -20°C) | |
Relative humidity: | <90%(20°C) |
Altitude: | ≤1000m |
NORMAL WORKING CONDITIONS: | |
Genset can run at rated power on the conditions: | |
Atmospheric Pressure: | 100kPa |
Ambient Temp: | 20°C |
Relative Humidity | 30%. |
APPLIED GAS: | Natural Gas, Biogas,Oil field gas |
Acceptable gas pipeline pressure: | 0.8~450kPa |
Engine inlet pressure: | 0.8~5.0kPa (80~500mmH2O) |
CH4 content: | for natural gas ≥75%; for biogas≥40% |
Sulphur content: | ≤400ppm |
Gas heat value: | ≥5500kcal/Nm3 (23MJ/Nm3 ) |
Genset output power will increase as the gas heat value increase, if use low heat value gas for fuel(Heat value<5500kcal/Nm3, it will lower the power efficiency.Gas doesn't include free water or free materials (the size of impurities should be less than 5μm.) |
1. Brand new gas engine, 90% parts include engine body , crank shaft, cam shaft, piston, cylinder head, etc made by Cummins with best quality |
2. Brand new brushless France Leroy Somer alternator |
3. Rating: 3 phases 4 lines. 400/230V, 50 HZ , 1500rpm, 0.8PF, IP22-23, Insulation class H |
4. Radiator for 40°C/50°C ambient temperature |
5. Ignition system adopted USA ALTRONIC |
6. Emergency stop mounted |
7. Battery,Battery cable and Battery charger |
8. Standard tool box |
9. Standard Accessory for installation (include bellows,silencer,flange,asbestos pad,Anti-rust water,screw ) |
10. Gas Train include Regulator valve,Electromagnetic Valve, Fire arrestor,Ball Valve (Chinese brand) |
11. Testing report and maintenance manual. |
1.Generator set parameter
Model | 120GFT |
Rated power | 120kW/150kVA |
Basics electric parameter | 50/60Hz,3 p 4 w,440V/230V |
Rated speed | 1500/1800rpm |
Power factor | Lag0.8 |
Insulation Class | H |
Protection Class | IP23 |
Gross Weight | 1950KG |
Dimension(L*W*H) | 2850*1000*1750mm |
2.Engine parameter
Engine Model | NC83D14TL | Cylinder Qty | L6 |
Rated power | 140kW | Bore*Stroke | 114*135mm |
Rated Speed | 1500/1800rpm | Displacement | 8.3L |
Fuel gas intake pressure | 2kPa--50kPa | Fuel gas type | Natural gas |
Engine Type | V type 4 stroke, electric control ignition,Pre-mixed stoichiometryburn |
3.Alternator parameter
Brand | MBH( Germany) | Rated Frequency | 50/60Hz |
Model | XN274FS | Rated output | 400V/230V |
Rated Power | 120kW/150kVA | Exciting Mode | Self-Excited,Brushless |
Rated current | 216A | Voltage Regulation | AVR |
4.Genset Controller introduction
Main Protection Function | Main Displayed Parameter | ||
Fail to start | Over speed | L-L&L-N voltage | Speed and running hours |
Low engine oil pressure | High engine temperature | Rated outputload current | Engine oil temperature |
Generator low frequency | Generator high frequency | Frequency | Engine oil pressure |
Generator low voltage | Generator high voltage | Load power | Coolant temperature |