Instruction manual of M-6007 input and output module
A. Features:
1.Built-in product ID code 2.Using hardware and software filtering technology to improve the module's anti-jamming capability 3.Linkage, 2 bus type, nonpolarity
WARNING: Before installing the device, turn off power. 1. Before installation should first check whether the shell is intact, logo is complete. 2. Install the module in the terminal box as shown in Figure 2. 3. Wiring: Figure 3 and Figure 4
Figure 3: method diagram of high-voltage high-power equipment controlled by M-6007
Figure 4: FW19110 wiring diagram Special warning: low-voltage low-power devices directly controlled by the module should meet the following conditions:
Working voltage range:18~30V(recommended 24V)
Working current:≤1.5A
3.Wiring requirements: Wire (bus) should be RVS-2 * 1.0 mm2 or 1.5 mm2; The DC24Vpower line uses the BV-2 * 1.5 mm2 or 2.5mm2 line; the normally open output line uses the BV-2 * 1.5 mm2 or 2.5mm2 line; RVS-2 * 1.0 mm2 or 1.5mm2 line for the feedback (BUS).
E. Use and operation Encoding operation: you can use our company's hand-held encoder P-6010 to live coding. When encoding, connect the two clips of the encoder to the two terminals of the linkage, open the handheld encoder power, enter the address code to be written (address code range must be: 1-242, the address code for the same loop is unique). For details on the steps and methods of encoding, refer to the "P-6010 Handheld Encoder User's Manual". .
F. Note
1. If the module reported fault after the long-term operation, first check whether the module is damaged, or whether the installation location is changed that not should to be, and then consider other fault of the module. 2. When the controller detects the cleaning forecast, please send the number of smoke detectors back to the company for cleaning, in order to avoid false or false positives, resulting in unnecessary losses.