11kv 1500kVA Power Transformer High quality/High cost performance Electrical Distribution

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 500 ~ 10000

Description
General

This product can be used in a wide range of areas, especially in the place of high fire protection requirements. ie, mine, oilfield, subway station, power plant, school, shopping center, skyscraper, and all indoor configuration systems.

 

STRUCTURE CHARACTERISTICS:

  • Iron core: core applies excellent cold rolling oriental silicon sheet and a 45°wholly sloped joint with no punching hole structure; the surface of the core is coated with a special resin to protect against rusting, and elastic materials are cushioned between the clamping parts and core, between the clamping parts and core, between coils and between the core and the base seat to reduce operation noise.
  • Coils: low voltage winding applies double cylinder type or fossil type, high voltage winding applies sectional connection type structure; which is wounded by F class insulated polyester double fibre glass copper conductor and reinforced by fiberglass, epoxy resin proportion is poured and moulded under vacuum state. It has good electric performance and mechanical strength.
  • Temperature control: apply automatic temperature control protection system; realize temperature display, patrol inspection, start and stop air fan, over temperature alarm,tip and communication interface of computer etc functions on demand of users.
 


References:

ISO 1461: Hot dip galvanized coatings on fabricated iron and steel articles - Specifications and test methods.
IEC 60076: Power transformers.
IEC 60044: Instrument transformers.
IEC 60296: Specification for unused mineral insulating oil for transformers and switchgear.
IEC 60354: Loading guide for oil - immersed power transformers.
IEC 60214: Tap-changers - Part 1: Performance requirements and test methods, Part 2: Application guide.
IEC 60512: Connectors for electronic equipment.

 


Technical specification:
 
Rated capacity (kVA)voltage combinationVector groupLosses(120°kW)No-load current(%)
HV(kV)tapping rangeLV(kV)On-load lossNo-load loss
30    0.710.193.2
50    10.272.8
80    1.380.372.6
100    1.570.42.4
125    1.850.472.2
160    2.130.542.2
2006   2.530.622
2506.3   2.760.722.2
3156.6±5% Yyno3.470.881.8
40010 0.4 3.990.981.8
50010.5±2x2.5% Dyn114.881.161.8
63011   5.881.341.6
630    5.961.31.6
800    6.961.521.6
1000    8.131.771.4
1250    9.692.091.4
1600    11.732.451.4
2000    14.453.051.2
2500    17.173.61.2




 
Rated capacity (kVA)voltage combinationVector groupLosses(120°kW)No-load current(%)
HV(kV)tapping rangeLV(kV)On-load lossNo-load loss
50    1.230.32.3
100    1.980.471.9
160    2.460.581.7
200    2.930.641.6
250    3.40.731.5
315 ±5% Yyno4.060.841.4
40020,22 0.4 4.8211.3
50024,10±2x2.5% Dyn115.761.171.3
63011,12   6.81.321.2
800    8.221.521.1
1000    9.731.791
1250    11.482.061
1600    13.792.410.9
2000    16.292.80.9
2500    19.273.340.8