CONTROL PANEL
The fire panel must be sited internally, in an area
where it is readily accessible by staff on duty and the
fire brigade. The area should be clean and dry and
you should take into account any likelihood of
tampering or vandalism. The ambient light and
sound levels should allow the status of the indicators
to be clearly seen and the internal sounder to be
heard. Full details can be found in BS 5839: Pt1: 1988:
Section 15.3 "Fire Detection and Alarm Systems for
Buildings".

External (key-switch operated):

  • Reset/resound/test zone lamps evacuate
  • Silence alarm sounders
  • Silence fault sounders

Internal:

  • One man detector test
  • Zone isolate
  • Revert to short-circuit: fire (no resistors in call points)

External indicators:

  • Sounder fault
  • Battery/power supply fault
  • Mains on
  • Zone fire
  • Zone fault

Internal indicators:

  • Open circuit zone fault
  • Short circuit zone fault
  • Zone isolated
  • Engineer test selected

Outputs:

  • Two sounder circuits (alarm relay contacts can be obtained by connecting a relay to a sounder circuit)

Ancillary connections for expansion modules will allow the following:

  • Repeater panels
  • Multiple sounder outputs
  • Connection to landlord panel


 

 Specifications 


 2 (0.8A supply)4 / 6 (1.5A supply)8/10/12/14/16/18
(4.0A supply)
Power specifications  
Mains supply voltage230±10%V AC, 50/60Hz230±10%V AC, 50/60Hz230±10%V AC
50/60Hz
Internal power supply27V DC27V DC27V DC
Total output current limited to800mA at 240V AC1500mA at 240V AC4000mA at 240V AC
Auxiliary power output27V DC27V DC27V DC
Mains supply monitored for failureYesYesYes
Battery charger monitored for failureYesYesYes
Batteries monitored for disconnection and failureYesYesYes
Detector circuit specification
Number of circuits24 or 68, 10, 12, 14,16,or 18
Line fault monitored for open circuitYesYesYes
Line fault monitored for short circuitYes (can be disabled)Yes (can be disabled)Yes (can be disabled)
Line fault monitored for detector removalYes, if end of line monitor unit fitted in place of end of line resistor
End of line resistor (supplied) value6.8K Ohm, 5% tolerance, 0.25W6.8K Ohm, 5% tolerance, 0.25W6.8K Ohm, 5% tolerance, 0.25W
Detector continuity diodesSilicone 1N4001 or Schottky type (required if end of line monitor unit fitted to give detector removal fault)
Call point resistor value (not supplied)470 to 680 Ohm, 0.5W470 to 680 Ohm, 0.5W 470 to 680 Ohm, 0.5W
Maximum number of smoke detectors per zone20 (maximum detector current = 2mA)  20 (maximum detector current = 2mA)  20 (maximum detector current = 2mA)  
Maximum number of manual  call points per zoneNo limitNo limitNo limit
Sounder circuit specifications:
Number of circuits222
End of line resistor value6.8K Ohm, 5% tolerance, 0.25W6.8K Ohm, 5% tolerance, 0.25W6.8K Ohm, 5% tolerance, 0.25W
Line fault monitored  for open circuitYesYesYes
Line fault monitored for short circuitYesYesYes
Outputs fused at1A1A1.6A
Maximum total output current all outputs 800mA 1500mA4000mA
Maximum no of bells at 25mA each bell3256120
Maximum no of electronic sounders at 20mA40 70 150 
Auxiliary relay contacts  (do not connect mains voltages)1A 30V DC max  
voltage free
1A 31V DC max  
voltage free
1A 32V DC max  
voltage free
Fuses-all fuses compliant to ice (EN60127 PT2)  
Mains terminal block200mA/T 20mm400mA/T 20mm630mA/T 20mm
Sounder outputs1A/F 20mm 1A/F 20mm1.6A/F 20mm
Auxiliary output1A/F 20mm1A/F 20mm1A/F 20mm
Battery fuse1.6A/F 20mm1.6A/F 20mm 3A/F 20mm 
Door retaining magnetsdo not use panel power supply as you will drastically reduce battery standby time
Connection block  
Largest acceptable2.5mm22.5mm22.5mm2
Smallest acceptable conductor size0.75mm20.75mm20.75mm2 
Dimensions 
Enclosure (width x height x depth)415 x 265 x 100mm415 x 265 x 100mm415 x 265 x 100mm
Weight (without batteries)5100g5200g5500