VLF(R) -12 Vacuum Type Load Breaker Switch with Fuse Combination

Min.Order: 1
Product origin: Baoji, Shaanxi, China
Infringement complaint: complaintComplaint
US$ 1800

Description

VLF(R)-12 Vacuum Type Load Breaker Switch with Fuse


General description
VLF(R)-12 vacuum load switch and fuse composite apparatus is an independently researched & developed new generation medium voltage switch products on the basis of extensively and profoundly market research and analysis, and combined with the generality of vacuum switch at home and abroad. It adopts HV fuse which can break a wide range of short circuit fault current within 10ms and matched with vacuum load switch.It can be used in transformers control and protection of transportation, chemical industry, petroleum and living community, especially transformers in 7.2KV~330KV range area and substation used small capacity transformer control and protection, so as to achieve remote operation and monitoring.




Outline drawing


Applying ambient conditions
a)Ambient temperature:-35~+40ºC
b)The height above sealevel:for 12kV is not exceed 1500m, for 7.2kV is not exceed 2000m.
c)Relative humidity:daily average relative humidity≤95%,monthly average relative humidity≤90%
d)Saturated vapour pressure:daily average value2.2kPa,monthly average value≤1.8kPa
e)Earthquake intensity:not exceed 8 degrees


Technical characteristics
VLF(R)-12 vacuum load switch and fuse combination apparatus adopts the three dimensional "Solidwork" software for design, 
using computer simulation technology to carry out preinstallation of each scheme during designing process,which provides reliable
guarantee for the improvement of thoughts of experts and technical personnel and scheme optimization.


Modular and mold produced mechanism is with clear integral structure,beautiful,complete functions,simple operation and maintenance,
reliable running etc.


Vacuum interrupter adopts vertical arrangement, which overcomes the gravity for dynamic conductive rod and moving contact inside the vacuum interrupter when horizontally installed. Vacuum interrupter outside selects the umbrella skirt & large creepage distance type, which overcomes the effects of environment on it.For plateau type it can choose casting embedded type,so as to achieve higher external insulation performance.



Reliable striker tripping module
The striker tripping module designing can guarantee that the load switch breaks fault current with reliable after the fuse fusing.
Fuse short circuit breaking fault is generally within 10ms(half a cycle), and the breaking current can be up to 50kA,with reliable
and efficient protection for transformer.



The fuse installation, fastening and heat radiating
High-voltage fuse is as shown in the right side picture, with the specific operation method as follows:firstly loosen the fuse grip of the main insulation part,and insert the fuse into front insulation part,impacting end is the direction of mechanism, and threads & fastens the screw clockwise, then locks the grip and process is completed. To replace the fuse, firstly loosen the fuse grip of the main insulation part, and then counterclcokwise rotates the front insulation part, the process completes. When it is running, the poles have column cooling holes on top, timely eliminates the heat from fuses, which guarantees reliable electrical performance and service life of the high voltage fuse.


Energy saving and environment protecting product
VLF(R)-12 vacuum load switch is with spring energy storage type operating mechanism. When meeting short circuit faults, it can achieve protection through primary fuse and mechanism, without applying secondary power supply, so it omits the conventional power supply such as UPS, DC screen etc., which is a kind of energy saving and environment friendly product.


Main technical specification
Item Unit Data
open distance between contactsmm8-10
contacts pressure spring strokemm3-4.5
distance between phases mm150/210/275
out of simultaneity of C/O operationsms≤2
contact bounching duration at closing operationms≤1
average closing speedm/s0.4~0.8
average opening speedm/s1.0~1.4
closing timems≤60
opening timems≤30
main circuit resistance≤100(280)
wear thickness of moved and fixed contactmm3
S.N.NameUnitVLF-12
load switch
VLFR-12
load switch
         VLF-12
vacuum circuit breaker
1rated voltagekV121212
2rated power frequency withstand voltage 1minkV424242
3rated lighting impluse withstand voltagekV757575
4rated currentA630125630
5rated short circuit breaking currentkA 5025
6rated short circuit withstand currentkA20 25
7rated peak withstand currentkA50 63
8rated short circuit making currentkA50 63
9rated cable charging breaking currentA30  
10rated breaking transfer currentA 3150 
11breaking no-load transformerkVA12501250 
12electrical endurancecycles100001000010000
13partial discharge magnitudePC≤5≤5≤5


Overall outline drawing