China Manufacture Intelligent Addressable Fire Alarm System for Fire Security

Min.Order: 1
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ 380 ~ 450

Description
Installation and Operation Manual

FW6000 Fire Alarm Control Panel


FW6000 Intelligent Fire Alarm Control Panel (FACP) is the new-generation fire alarm control unit designed by our company for applications in small and medium projects. It is wall-mounted type and has the advantages of powerful function, high reliability and flexible configuration. The panel is equipped with a LCD monitor to display all the information on fire alarms, faults and various operations, which can be printed out by the built-in printer. FW6000 is a one-loop control panel with maximum 240 points, which can work together with all FW 3 series field devices.

Note: COM port needs grounding
1,(Monitoring Start Output)HJ: Active NO terminal to Fire alarm routing device (use jumper to switch  
between passive and active), which will close to connect +24V output after started (each points with a
max output current of 100mA)
2,(Monitoring Start Output)SG: Active NO terminal to Sounder Strobe (Both active and passive modes,  
use jumper to switch between passive and active), which will close to connect +24V output after
started (with max output current of 100mA for each direct-start point)
3,BUS: Non-polarity two-wire bus terminal
4,Linkage power supply output: 24VDC(Max output current 1A)
5,Main board power supply input: 220VAC
6,Grounding Terminal: Grounding
 
2.4 Technical Specifications
2.4.1 Power Supply:
AC power: Nominal operation voltage 220VAC (187VAC ~ 242VAC)
Standby Battery: 2 x 12V/12AH
2.4.2 Operating Environment:
Temperature: 0ºC~+40ºC
Relative Humidity: ≤95%, non-condensing
2.4.3 Capacity: One loop with maximum 240 devices
2.4.4 Display: LCD 128×64 lattice graphic
2.4.5 Dimension: (Length ×Width ×Height):330.0mm×130.0mm×400.0mm
2.4.6 Wiring requirement
1,Recommend to use RVS2×1.0MM2 or RVS2×1.5MM twisted wire for CAN communication wire and bus  
wire, while use RVSP2×1.0mm2 at the high interference environment.
2,Not allowed to lay CAN communication wire and telephone line together with bus wire inside the same      
  multi-core cable.


Product Tag:
Related categories:
Scroll to Top