DC SUPPLY CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous
CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT 100 mA at 12 V, 105 mA at 24 V
MAXIMUM STANDBY CURRENT 60 mA at 12 V, 55 mA at 24 V
MAXIMUM SLEEP CURRENT 40 mA at 12 V, 35 mA at 24 V
INPUTS DIGITAL INPUTS A to F Negative switching
ANALOGUE INPUT A Configurable as: Negative switching digital input 0 V to 10 V 4 mA to 20 mA 0 Ω to 240 Ω
ANALOGUE INPUTS B to D Configurable as: Negative switching digital input 0 Ω to 480 Ω
FREQUENCY RANGE 3.5 Hz to 75 Hz
Testing Standard
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1 Ab/Ae Cold Test -30 oC BS EN 60068-2-2 Bb/Be Dry Heat +70 oC
VIBRATION
BS EN 60068-2-6 Ten sweeps in each of three major axes 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30 Db Damp Heat Cyclic 20/55 oC @ 95% RH 48 Hours BS EN 60068-2-78 Cab Damp Heat Static 40 oC @ 93% RH 48 Hours
SHOCK
BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 mS
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529 IP65 - Front of module when installed into the control panel with the supplied sealing gasket.
CONNECTION DIAGRAM
Other Controllers
Generator controller brands
Deep sea , Comap ,and Smartgen
DEEP SEA Genset Generator Auto Start Control Modules: