12kv 50Hz Outdoor Column Intelligent Vacuum Circuit Breaker

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 1500 ~ 10000

Description
GENERAL
Zw32-12y series outdoor high-voltage AC prepaid metering vacuum circuit breaker (hereinafter referred to as "prepaid circuit breaker") is an outdoor high-voltage distribution switchgear with a rated voltage of 12kV and three-phase AC 50Hz. According to the user's requirements, the high-voltage metering box of the prepaid circuit breaker can be a three-phase three-wire system (V / V wiring) or a three-phase West wire system (Y / y.no wiring). The metering current transformer can be a single transformer with a ratio range of (2.5 ~ 1200) / 5

The prepayment circuit breaker body and the high-voltage metering box are designed in an integrated manner. The control box is composed of the prepayment meter and the high-voltage circuit breaker control circuit. It can be installed with a prepayment meter for prepayment measurement according to the user's requirements, and it can also be installed with a YDG power consumption management terminal. The circuit breaker can be directly controlled by the background, and real-time shop parameters and switch status can be queried.

Prepaid circuit breakers comply with GB / T 1984-2014 high voltage AC circuit breakers, DL / T 402-2016 voltage AC circuit breakers, DL / T 403-2000 technical conditions for ordering 12kV ~ 40.5kV high voltage vacuum circuit breakers, and GB / T 20840.2-2014 transformer part 2: supplementary technical requirements for current transformers, GB / T 20840.3-2014 transformer part 3: supplementary technical requirements for electromagnetic voltage transformer and DL / T 403-2013 distribution automation remote terminal and other technical standards.


MODEL DESCRIPTION

USAGE: ENVIRONMENTAL CONDITION
  1. Altitude:  1000m, If the altitude is higher than 1000m, the rated insulation level shall be corrected accordingly.
  2. Ambient temperature: -40oC ~ +45oC, 
  3. Maximum daily temperature difference: 25K 
  4. Humidity: Average daily relative humidity: 95%, average monthly relative humidity: 90%. 
  5. Sunshine intensity (at wind speed of 0.5 m / s): not more than 0.1W/cm2 
  6. Wind Speed:  34m/s 
  7. Wind pressure: 700Pa
  8. Pollution level: e - level
  9. Icing thickness: Not more than 10mm 
  10. Resistance to floor drain: horizontal acceleration 0.3g, vertical acceleration 0.2g


MAIN ADVANTAGES

1. The overall structure is a three-phase pillar type, with good sealing performance, good moisture-proof and anti-condensation performance;
2. The shell (box) is made of SUS304 non-magnetic stainless steel, which is precision welded and polished by an imported arc welding machine, with a beautiful appearance and never rusts;
3. The integrated design of the high-voltage metering box and the switch body is simple and convenient for installation, and maintenance free and long service life;
4. The price operating mechanism has a novel design, simple structure, reliable action, and small volume;
5. It can realize the functions of three-stage protection, reclosing, remote communication, metering, and prepayment.


MAIN TECHNICAL PARAMETERS
 
No.ItemUnitData
1Rated frequencyHz50
2Rated voltagekV12
3Rated currentA630 / 1250
4
Rated short-time power frequency withstand voltage
Interphase, to earth(wet)kV/min34/1
Interphase, to earth(dry)42/1
Fracture (dry)48/1
Secondary circuit to earth2/1
5Rated lightning impulse withstand voltageInterphase, to earthkV75
Fracture85
6Rated short-time withstand current and durationkA/s20/4   25/4
7Rated Short-circuit breaking current(Effective value)kA20 / 25
8Rated short-circuit making current(peak)50 / 63
9Rated Peak-withstand current50 / 63
10Main circuit resistanceWithout Isolation SwitchμΩnot less than 80
With Isolation Switchnot less than 120
11Rated Short-circuit breaking current breaking timesTimes30
12Rated operating voltage and Rated Voltage for auxiliary(control) circuitVAC/DC220
DC48, DC24
13Mechanical lifeTimes10000 
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate.



OUTLINE AND INSTALLATION DIMENSION
 
 