Acrel Aid150 Digital Remote Indicators for Medical Isolated System

Min.Order: 1
Product origin: Wuxi, Jiangsu, China
Infringement complaint: complaintComplaint
US$ 92.4

Description
Product Description
AID150 Alarm And Display Device for Medical Isolated Power System




General
The alarm and display instrument AID150 is designed for visual and audible indication of alarm messages from ACREL medical intelligent insulation monitor AIM-M10, AIM-M100, AIM-M200, and Residual current monitor AIM-R100 . It meets the requirement of GB16895.24-2005/IEC 60364-7-710:2002.
60A input Protection current transformer for isolated electrical power supply in medical locations.
ACREL isolated power panels provide isolated power to electrical systems in operating rooms and other critical care areas.
Utilizing the latest in technology, ACREL hospital isolated power supply monitor system ensures that electrical ground faults are detected and located fast and automatically.
It is CE approved,in application for IEC standards,it could be the equivalent to Bender isolated power supply IPS for healthcare facilities,and more cost-effective.



Features
1.LED (green) for indicating the operating status , 1 LED(green)for communication, 1 LED (yellow) for error, and 1 LES (red)for alarms.
2.Audible alarm (can be muted by pressing mute button).
3. AIM-M series IMD can be tested by pressing the test button of AID150.
4. Communicate with the maximum of 16 AIM-M or AIM-R series devices via RS485 bus with Modbus-RTU protocol.
5. Display the operating status with LCD.
6.Installation of embedded wall



Technical Parameters
VoltageDC18~36V
Consumption≤0.6W
Insulation alarm range50…999kΩ
Current alarm range14A,18A,22A,28A
Alarm modeAudible and visual alarm
Alarm typeInsulation fault, overload, overtemperature, device disconnection
Display modeLCD
History memory20
InterfaceRS485
ProtocolModbus-RTU
Maximum of IMDs or RCMs16

Dimension(Unit:mm)



Display


Wiring





Typical Connection




Quotation