Acrel Ard2f-25/C+90L Smart LCD Display RS485 Modbus Motor Protector Motor Protection Relay

Min.Order: 1
Product origin: Wuxi, Jiangsu, China
Infringement complaint: complaintComplaint
US$ 105.7

Description
Product Description

ARD2F Smart Motor Protector

General

ARD series intelligent motor protector (hereinafter referred to as protector) can perform various conditions such as start
timeout, overload, phase failure, unbalance, underload, ground/leakage, blockage, short circuit and external fault during motor operation. Protection, and SOE fault event recording function, convenient for on-site maintenance personnel to find the cause of the fault. Suitable for coal, petrochemical, smelting, electric power, ships, and civil construction. The protector has RS485 remote communication interface, DC 4 ~ 20mA analog output, and PLC, PC and other control machines form a network system. Remote monitoring of motor operation.



Features
1.Measurement functions are divided into basic measurement (current parameter) and co-selection measurement (voltage, power, phase sequence, residual current (leakage current);
2.Start timeout, overload, stall, block, underload, phase failure, unbalance, residual current (ground/leakage), temperature,
3.external fault, phase sequence, overvoltage, undervoltage, underpower, overpower, tE time Motor comprehensive protection function;
4. 9-channels DI passive dry node input, signal power supply with built-in DC24V power supply;
5.5-channels DO output, which can meet the direct start, star-delta start, autotransformer start, soft start and other starting modes. Real-time remote control "start/stop" operation of the remote master station can be realized through the communication bus;
6.It has standard RS485 communication interface and adopts Modbus-RTU and Profibus-DP communication protocol to ensure fast and reliable communication of the host computer;
7.It has a DC4-20mA analog output interface and is directly connected to the DCS system to monitor the field devices.

Technical Parameters
Technical data of motor protector ARD2F-25
Auxiliary power supply of protectorAC85V~265V/DC100V~350V, power consumption ≤7VA
Rated working voltage of motorAC380V/AC660V, 50H/60Hz
Rated working current of motor1A(0.1 ~9999)Small specific current transformer
5A(0.1 ~9999)
1.6A(0.4A-1.6A)
6.3A(1.6A~6.3A)
25A(6.3A~25A)
100A(25A~100A)
250A(63A-250A)Specific current transformer
800A(250A~800A)
Relay output contactor, rated load capacity4-way,AC250V, 3A, DC30V, 3A
Switching input2-way, optical isolation
CommunicationRS485 Modbus
Volume of SOE event recorder8 events
EnvironmentWorking temperature-10ºC-55ºC
Storage temperature-20ºC-65ºC
Relative humidity5%-95%, no dew
Altitude≤2000m
Class of pollution2
Protection levelIP20
Rated current of motor protector(A)current ratio settingTransformer primary side turnsSetting current Is range(A)Motor Power(kW)
1able to set50.1~99990.12~440
510.1~99990.12~440
1.6unable to set10.4~1.60.12~0.55
6.311.6~6.30.75~2.2
2516.3~253~11
100125~10015~45
250163~25055~132
8001250~800160~440
Function




Wiring




Typical Connection







Quotation





Certification






Product Tag:
Related categories:
Scroll to Top