HVHIPOT GDJB-III Single Phase Smart Relay Protection Test Set

Min.Order: 1
Product origin: Wuhan, Hubei, China
Infringement complaint: complaintComplaint
US$ 8000 ~ 15000

Description

GDJB-III Single Phase Smart Relay Protection Test Set


General Information

GDJB-III type Single Phase Relay Protection Test Set is the updated calibration device for relay testing. It shows clear data,operation is easy.

Features

1. Three-way output
Main output: fully isolated and adjustable AC and DC voltage and current output, short-circuit, overload, over-range automatic protection;
Auxiliary output: (1) DC: 0~220V power amplifier output, short-circuit, over-load, over-range automatic protection;
(2) AC: 0~120V power amplifier output, short-circuit, overload, over-range automatic protection;
0~8A power amplifier output, short circuit, overload, over-range automatic protection.
2. Maximum output current: 0~250A.
3. Equipped with a large LCD screen digital AC and DC voltammeter, which can display AC and DC voltage and current values, stopwatch, potential and contact status.
4. Equipped with measurement input meter, which can be used as voltmeter and ammeter;
5. The internal electric stopwatch can work with live contact, the potential is up to 250V, and two-way measurement.
6. Small size, light weight and multi functions.





Specifications
1. Power supply: AC 220V±10%, 2000VA, 50Hz
2. AC output
Range(A)No-load voltage(Min.) VFull load voltage(Min.) VFull load current (Max.) A
0~1511010015
0~60282560
0~20087200
0~250 (AC)2502406
0~300(DC)3002504

3. DC auxiliary output
Range VVoltage VMax. Current A
0~1101200.5
110~2202200.5

4AC auxiliary output
Range Voltage VMax. Current A
0~110V1200.4
0~3A58
Phase shiftable or variable frequency output

5Timer
Range: 0.0000~999,999s , resolution: 0.1ms, accuracy: ±5 digitals
With contacts and potential input, the maximum input voltage: DC 250V

6.Ammeter
Range: internal 0.000~250.0A (AC or DC)

       external:0.000~6.000A (AC or DC)
Accuracy: 0.5%
Measurement method: AC: TRMS,  DC: average value

7.Voltmeter
Range: 0.0~600.0V (AC or DC), accuracy: 0.5%

Measurement method: AC: TRMS,  DC: average value

8.Resistance & Capacitor
Resistance: 0.5Ω~2.5kΩ, capacitor: 10uF, Max. Voltage AC 450V


9. Open / close auxiliary contact
Max. current: 1A, max. voltage: AC250V or DC120V

10.Operating environment: temperature -10~40 ºC, relative humidity less than 80%

11.Volume: 400 mm × 300 mm × 280 mm

12.Weight: 28kg






Product Tag: