New Arrival Product PV-MCU En54 Main Function Control Unit with Audio Storage and Monitor for Fire Alarm System

Min.Order: 10
Product origin: Guangzhou, Guangdong, China
Infringement complaint: complaintComplaint
US$ 1300 ~ 1500

Description

New Arrival Product PV-MCU EN54 Main Function Control Unit with Audio Storage and Monitor for Fire Alarm System 

Model Number: PV-MCU EN54

Description:

Master Control Unit (MCU) is the central management device of the system, which is used to manage and monitor all devices and performvarious operations. MCU is integrated with audio storage, broadcast, zone control, monitor, timing control, fault diagnosis, etc. functions. Built-in 500W digital power amplifier can drive maximum 8 loudspeaker lines to meet requirements for small applications. It can also be connected to zone expanders to increase system capacity for the requirements of large applications as well.

Features:
  1. Complies to international standards.
  2. Plug-and-play for easy commissioning.
  3. Fully configurable keys to achieve any task at the press of a button.
  4. Modular architecture: Expandable up to 128 speaker lines.
  5. Dual channel audio capability.
  6. Flexible amplifier backup modes to ensure low cost of ownership and high reliability.
  7. Digital volume control on all inputs/outputs.
  8. Comprehensive fault detection and indication.
  9. With EN54 certificate




                 




   






     
Specification PV-MCU EN54
 Parameters Values
 Main Supply Voltage  AC 220-240V, 50/60Hz
 Backup Power Supply Voltage AC 220-240V, 50/60Hz
 Main Power Supply Fuse T10AH 250V
 Power Consumption <760W
 Microphone Input
 Input Sensitivity -59±3dBV
 Input Impedance 250Ω
 Frequency Response 100Hz-14KHz, ±3dB
 SNR >50dB
 Auxiliary Input
 Channels 2
 Input Sensitivity 1V(0dBV)
 Input Impedance 10 KΩ
 Frequency Response 85Hz-18KHz, ±3dB
 SNR >80dB, A-weighted
 Phantom Power 24V DC, set by DIP switch
 Call Station Interface
 Input Signal 2V
 Input Impedance 20KΩ
 Output Signal 2V
 Onput Impedance 20KΩ
 Frequency Response 85Hz-18KHz
 Audio Output
 Output Channels Channel 1, channel 2 and recording output
 Output Signal  1V(0dBV)
 THD <0.1%
 Amplifier Control Interface
 Channels 3 (channel 1, channel 2 and backup amplifier)
 Output Signal 1.4V
 THD <0.1%
 Control Signal  Self-test Signal, amplifier fault, signal and power saving control signal
 Loudspeaker Circuit
 Output Channels 8 (with group A and Group B)
 Maximum Loudspeaker Load 500W
 Contact Input / Output
 Contact Inputs 10 contact input interfaces with supervision
 Contact Outputs 8 (NO, NC&COM), fault output, emergency output
 Max. Working Voltage for Output AC 250V/ DC 30V
 Max. Working Current for Output 2.5A
 Others
 DC Power Output 24V/1A
 Monitoring Loudspeaker 2W/8Ω
 Ethernet Port 10M/100M
 Memory Capacity 1GB flash memory, 4GB SD card
 Operating Conditions
 Humidity <95%, without condensation
 Operating Temperature -10ºC~+50ºC(14ºF to +122ºF)
 Storage Temperature  -40ºC~+70ºC(-40ºF to +158ºF)
 Weights and Dimensions 
 Product Dimension (W*H*D) 482*133.5*420mm
 Package Dimension (W*H*D) 580*279*552mm
 Net Weight 14.3KG
 Gross Weight 17.4KG
         
                                                                                   







Scroll to Top