Product Description
§ This emergency kit works as an isolated circuit, voltage: AC220-240V, the output is constant current
§ The self-regulated internal charger keeps the battery fully charged and protects it from overcharging.
§ Li-on battery, Non-Mantained.
Product Specification
Item | Model | LEK08-924LF |
Input | Working Voltage | AC220-240V |
Output
| Appliacable | T8 LED tubes with internal LED driver |
Working Power | 9W, 18W, 24W | |
Output Voltage | DC220-240V | |
Supply Current | 0.8A-2A | |
Charging Time | >24H | |
Emergency Duration | 60-120 minutes | |
/
| Storage Temperature | (-20~+ 85°C 10-85% RH) |
Ambient Temperature | ( -10~45°C) standard tempearture 25°C | |
Dimensions | 230mm X 32mm X 30mm |
Wiring Diagram
Important Notes
:: Exceeding the storage and usage temperature range will shorten the life of the battery.
:: The battery must be charged and discharged at least once every 3 months.
:: Use only the original battery connector. Do not attempt to solder directly on the battery.
:: The battery must be used only in the specifiED temperature range.
:: Do not subject the battery or equipment to shocks.
:: Do not place the battery in contact with fire or attempt to disassemble it. The battery content is highly alkaline and may damage skin or clothing.
:: When the emergency function test is finished, the battery should be disconnected firstly before removing the kit!
Description of indicator lights and test button
Indicator Light
| Green light | In the presence of mains electricity supply, constant green light on. |
Red light | The red light is becoming brighter during charging, and keeps constant red light on after Battery fully charged. | |
Yellow light | Battery disconnected, yellow light accompanied by alarm sound signal. | |
Test Button | ≤1S | To test the equipment load: (Press and release the button) to change the mode of operation, (AC and emergency battery). |