36kv Indoor Sf6 Load Break Switch Lbs Sf6 Gas Insulate Disconnector

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 700 ~ 1800

Description

++++General:

    RLS-36 an indoor high-voltage SF6 load switch, an swi tchgear wi ththe rated voltage of 36kV/40.5kV, adopted wi th SF6 gas as an arc-extinguishing and insulation medium, including the three contactors for switching-on and switching-off andto-ground, and is characteristic in its small volume, its convenient installation and operation and itsthe great adaptability with surroundings. RLS-36 of an indoor high-voltage SF6 load switch and RLS-36 of SF6 load switch plus fuse combination canfunctionto protect and controlthe electric equipmentsfor power supply andtransformer substations especially being suitable for ring net cabinet, cable branch cabinet and distribution switching substation. 

    RLS-36 of an indoor high-voltage SF6 load switch and RLS-36 load switch plusfuse combination are complied withthe standards of GB3804-1990, IEC60256-1,1997, GB16926, IEC60420 etc.. 


++++Service environment:

    a) Airtemperature Maximumtemperature: +40ºC; Minimumtemperature:-5ºC
    b) Humidity Monthly average humidity 95%; Daily average humidity 90%. 
    c) Altitude above sea level Maximum installation altitude: 2500m 
    d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 
    e) Nofrequent violent shake

++++ Main technical specifications:

 No

  Item

  Unit 

 Parameter

  1 

  Rated voltage 

  kV

  36

 2 

  Rated frequency

 Hz 

   50/60

 3 

  Rated current

  A

  630

 4

                                                 wet

 1min Power frequency withstand voltage 

                                                 dry

  kV 

 

 kV

  95 

 

 110  

 5

  Lightning impulse withstand voltage 

  kV 

  185/215

 6

  Rated short circuit breaking current (peak)

  kA

 50

  7 

        Rated activeload and close circuit breaking current

  A 

  50

 8

 Rated transferring current 

  A 

  1000

 9 

  Rated short circuit making current (peak) 

  kA 

  50

 10

  Rated cable(line) charging breaking current

  A 

  50 and 10

  11 

  Cable charge breaking current in earthing fault 

 A

  20

 12

 Rated withstand current (peak)

 kA

  50

 13

 Short time withstand current (2s)

    kA

  20

 14

  Mechanism life

 times

 2000





 
Scroll to Top