sharp price secondary injection relay test set instrument for protection relay
Brief introduction Secondary current injection test set not only used for test all traditional relays and protection devices, but can also carry on all kinds for modern various microcomputer protection, especially for transformer differential protection and automatic transfer switch equipment.
Main Features
Six phase voltage and six phase current can be output, which has made it is possible to be any combination.
Available to connect with acomputer or a desktop compute directly .
Output port with high fidelity and high reliability function and excellent performance.
The output part adopts DSP control, which has fast operation, real-time digital signal processing capability, wide bandwidth and high resolution D/A conversion control.
It can complete all kinds of high automatic validation work which is large and complex.
110V and 220V adjustable DC power is designed to supply output.
With USB communication port can communicate with the computer and other external devices.
With power soft start function and the software of the fault self-diagnosis and the output latch function.
DC Output current:10ADC per phase AC output voltage:120VAC per phase DC output voltage :160VDC per phase
Parameter
Type
Total Current channels
Six phases
Total Voltage channels
Six phases
AC Output current
30A per phase or 180A (six phase parallel)
DC Output current
10ADC per phase
AC output voltage
120VAC per phase
DC output voltage
160VDC per phase
AC current output Output current per phase under 6-phase output: 0~30A output precision 0.1 grade Output current per phase under 3-phase output: 0~60A Output current when 6-phase in parallel :0~180A Allowed phase current for long time working: 10A The maximum output power of phase current 450VA The maximum output power when 6-phase in parallel: 1000VA The allowed working time when 6-phase in parallel:10s Frequency range(fundamental wave): 0~1000Hz Harmonic times:0~20
DC current output Current output:0~±10A / phase output precision 0.2 grade The maximum output load voltage: 20V
AC voltage output Phase voltage output: 0~120V output precision 0.1 grade Linevoltage output: 0~240V Output power of phasevoltage/ linevoltage : 80VA / 100VA Frequency range(fundamental wave): 0~1000Hz Harmonic times:0~20
DC voltage output Phasevoltage output: 0~±160V output precision 0.2 grade Linevoltage output: 0~±320V The output power of phasevoltage/ linevoltage 70VA / 140VA
Input and output 8 channels input Idle contact : 1~20mA,24V Electric potential contacts: "0":0 ~ +6V; "1":+11 V ~ +250 V 4 pairs switch output: DC:220 V/0.2 A;AC:220 V/0.5 A
Time measurement range 0.1ms ~ 9999s , measurement accuracy <0.1ms