APC E3mups120khs UPS. Easy UPS 3m 120kVA 400V 3: 3 UPS

Min.Order: 1
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ 10541 ~ 21480

Description
Easy UPS 3S supplies power stability with robust electrical specifications and long-lasting performance to ensure your business continuity. Designed for fast and easy installation in the data center or electrical room, this EcoStruxure-ready UPS features a wide-operating temperature window and strong overload protection, all in a compact and lightweight footprint. These industry-leading features make Easy UPS 3S the easy choice for your business continuity.

Easy to install and start up
•   Rolls into position quickly
•   Minimal footprint requirement with lightweight, compact form factor
•    Straightforward installation:
-  Input, output, and bypass breakers are
included
-  Emergency Power Off (EPO) switch 
is included
- Easy Loop test verifies UPS performance
before you connect your load, without the need for a load bank
•    Aesthetic design blends well into your installation environment
•   Schneider Electric service team and certified service partners available to provide on-site start-up

Easy to use, monitor, and manage
•    User-friendly display interface supports easy configuration
•    With the optional SNMP card:
   Monitor UPS status remotely through a
Web interface  
-  Monitor and manage UPS status and
performance through EcoStruxure IT's cloud-based and on-premise software suites

Easy to expand
Parallel up to four UPSs for capacity or redundancy

Easy to maintain
Front access for service
•    Quickly and easily replace the dust filter conveniently located behind the magnetic front panel
•   Schneider Electric service team available to make service easy and deliver peace of mind
Typical applications
•    Small & medium data centers
and computer rooms
•    Manufacturing facilities
•   Telecommunication
•    Commercial buildings
•    Healthcare
•    Transportation

TECHNICAL SPECIFICATIONS
 
Rated Power (kVA/kW)60/6080/80100/100*120/120*200/200*
Normal AC supply input
Input Voltage (V) 380/400/415 V (Three-phase + Neutral)
Frequency (Hz) 45 - 65 Hz
Input Power FactorUp to 0.99
THDI <3.5% at full load
Input Voltage Range342 V to 477 V at full load
Dual Mains Input Yes (default: single main input)
Output
Nominal Output Voltage (V) 
3:3 - 380/400/415 V 
Efficiency: Double Conversion ModeUp to 96%
Efficiency: EcoMode0.99
Overload Capacity in Utility Operation 125% for 10 minutes, 150% for 60 seconds
Output Voltage Tolerance  +/-1% static
Communication and management
Communication Interface RS232, RS485, USB, Dry contact, Modbus TCP/IP, optional SNMP card
Control Panel Multi-function LCD, status and display console
Weights and dimensions
Low frame, unpackaged/shipping dimensions (H × W × D, mm)915 × 360 × 850 mm/  1140 × 475 × 965 mm915 × 360 × 850 mm/ 1140 × 475 × 965 mm915 × 360 × 850 mm/ 1140 × 475 × 965 mm1300 × 500 × 850 mm/ 1500 × 625 × 975 mm300 × 600 × 850 mm/ 1500 × 725 × 975 mm
      
Low frame, unpackaged/shipping weight (KG)109/133140/164145/169193/223304/338
      
Battery Catridge (coming soon) (1 string/4 modules), unpackaged/shipping weight   27 KG per module/28 KG per module
Regulatory
SafetyIEC/EN62040-1-1PerformanceIEC 62040-3
EMC/EMI/RFIIEC 62040-2EnvironmentalIEC 62040-4
Product Tag: