Product DescriptionADW210-D10-1S lcd display three phase multi channel smart IOT wireless modular submetering energy meter
General
ADW2XX series rail type multi-loop power meters are mainly used for measuring the full electric parameters of multiple three-phase circuits,Up to four three-phase loop current inputs can be connected simultaneously.It Can measure voltage and current, power, power factor, phase angle, unbalance, harmonic and other parameters. Function1.Full electric parameter measurement of N(1,2,3,4) three-phase circuit,externalCurrent transformer;
2.Monitoring three Phase Voltage/Current,Zero sequence Current,Frequency;
3.Monitoring three Phase power ,total power (active,reactive,apparent);
4.Monitoring three Phase power-factor,totalpower-factor;
5.Monitoring Voltage/Current Phase Angle,Voltage/Current Degree of unbalance;
6.Monitoring Voltage,Current total Harmonic and 2-31 Fractional harmonics;
7.Record of voltage,current and power extremum of current month and last month;
8.Maximum Current,Maximum power demand and real time Current,real time power demand;
9.200 event records,Record the action of DIDO;
10.Support over-voltage, over-current, phase failure,DI linkage and other alarm output;
11.4 time zones 14Periods rate setting;
12.Four quadrant electric energy,12-month multi rate electric energy;
13.31 days four quadrant and multi rate electric energy freezing,Positive and negative energy metering;
14.2 channel Switching inputs,2 channel Switching outputs,RS485,Active pulse output(Switchable corresponding circuit).
The following auxiliary functions can be extended through its RJ45 interface:15.(MK) 12 channel Switching inputs+4 channel Switching outputs;
16.(MTL) 12 channel external NTC temperature +4 channel residual current measurement (leakage current);
17.(AWT100-2G) 2G Wireless Communication
18.(AWT100-4G) 4G Wireless Communication
19.(AWT100-NB) NB-IoT Wireless Communication
20.(AWT100-LoRa) LoRa Wireless Communication
21(AWT100-LW) LoRaWAN Wireless Communication
Technical Parameters(Meter)Auxiliary power | AC/DC 85~265V;consumption≤10VA; |
input | Frequency | 45~65Hz; |
Voltage | AC 3×220V/380V; |
Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s; |
Power consumption:≤ 0.5VA; |
Current | AC 5A,100A,400A,600A;(External opening transformer) |
Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s; |
Power consumption:≤ 0.5VA; |
measurement accuracy | Frequency 0.05Hz, voltage and current 0.5 level, active electric energy level 1, reactive electric energy level 2; |
| 2-31 times harmonic accuracy: ± 1%; |
Features | Pulse output | Output mode: optocoupler pulse with open collector; |
Communication | RS485,Modbus-RTU;Baud rate 1200~38400; |
Switchin g | input | Dry contact input,Built in power supply; |
output | Output mode:Relay normally open contact output; contact rating:AC 250V/3A DC 30V/3A; |
Technical Parameters(Module)
Switching Module | Power | RJ45 interface,DC 12V,Power consumption≤1W; |
Communication | RJ45 interface,Modbus-RTU;(Communication with the main Part) |
Switching input | Dry contact input,Built in power supply; |
Switching output | Output mode:Relay normally open contact output; contact rating:AC 250V/3A DC 30V/3A; |
Temperature and leakage module | Power | RJ45 interface,DC 12V,Power consumption≤1W |
Communication | RJ45 interface,Modbus-RTU;(Communication with the main Part) |
temperature measurement | -20~100ºC; |
Leakage measurement | 10~3000mA; |
measurement accuracy | temperature ±2ºC,Leakage1.0%; |
Other Parameters Safety | Power frequency withstand voltage | >AC 2kV/1min; |
Insulation resistance | >100MΩ; |
Environment | working temperature:-20ºC~+60ºC; Storage temperature:-40ºC~+70ºC; relative humidity:≤95% No condensation; Altitude:≤2500m; |
electromagnetic compatibility | Better than grade 3; |
Dimension(Unit:mm)ADW2xx series main part dimensionModule dimensionDimension(CT)InstallationWiringQuotation