AC Pressure Power Frequenct Withstand Strength Hv High Voltage Test Instrument 100kv

Min.Order: 1
Product origin: Wuhan, Hubei, China
Infringement complaint: complaintComplaint
US$ -1

Description
I.Overview 
The equipment is suitable for measuring Dielectric Withstand voltage test, it includeds 1 manual controller and 1 test transformer (Oil type). It has superior performance,functionality and access to reliable,pleasing in appearance,easy operation and maintenance.

II.Schematic diagram of the structure and panel layout
The equipment shows the structure of box-type made from aluminum alloy.The equipment has simple alarm circuit,reliable performance with time setting and synchronous sound and light alarm function.

1.Panel layout:

1-Time Set          2-Low Voltage Current       3-High Voltage    
4-Ground             5-Meter                  6-Output                
7-Power Input      8-Overcurrent Protection      9-Close Indicator
10-Open Indicator   11-Zero Reading            12-Audible And Visual Alarm   
13-Switch         14-Output Regulation         15-Time Switch     
15-Stop           16-Start  

 2.Oil transformer   
       
18-Oil Cover           19- Power        20-Meter        21-Grounding  
22-Equalizer            23-AC ouptut     24- DC output




III.Advantage
1.Control unit
-Switch on sound and light alarms;
-Time sound and light alarms;
-Electronic low-voltage current protection;
-High voltage direct-reading;

-Voltage withstand test of time free to set up;
-Mobile structures


2.Oil transformer
-Epoxy resin vacuum casting and CD type iron core structure technology
-Small size, light weight and compact structure, noleakage, maintenance free;
-Simple wiring, easy to use;
-Reliable Insulation, beautiful appearance;
-Over voltage protection function

IV.Technical parameter

 Control unit:
  1. Capacity:10KVA
  2. Input Voltage:AC220V 50Hz
  3. Rated Input: 45A
  4. Output Voltage :0~250V
  5. Power Output :0~50A
  6. Size:49 x 38 x 39 cm
  7. Weight:GW/NW:40kgs/28kgs

  Oil transformer:
   1. Capacity:10KVA
   2. Input Voltage:AC220V  50/60Hz
   3. Power Input:50A
   4. Output Voltage:AC 0-150KV; DC 0-200KV (DC for option)
   5. Output current: AC 0-66mA; DC 0-47.5mA
   6. Transformer Ratio:1000
   7. Unload Loss :<10%
   8. Short circuit resistance:<10%
   9. Ratio error:<1%
  10. Meter voltage:100V
  11. Insulation oil dielectric strength:2.5mm,>50kV
  12. Accuracy:<2%(F.S)
  13. Size: 56*43*125cm
  14. Gross weight: 165kgs; Net weight: 185kgs.

     
V. Reference wiring Diagram
 
1.AC connecting:
        
TR-Test Transformer      Cx-Device under test (test object)
FRC-High voltage Divider (equipped by user) 
 
2.DC connecting:
 
VD-High-voltage silicon assembly  
R1-Current-limiting resistor(water resistor)   C1-High-voltage filter capacitor   
FRC- HV Divider     CX-Test object   μA-Micro-ammeter


VI. Application reference for AC/DC testing:
Sr noDescription QtySpecificationRemarks
AC TestDC Test

  1
     
Control unit

1 unit

  10KVA


 

  2
 
Test transformer

1 unit

  10KVA/150KV
 

3


Filter Capacitor *


1 unit

 
  DC 200KV


X
Cables: X
Transformer
Switchgear:
Generator:
 
4

Water Resistor *

1 unit

  DC 200KV

X

Unnecessary
 
  5

Microampermeter

1 unit

  0-19999µA 

X

 
  6

Discharging rod

1 unit

  100KV

X


  7

High Voltage Divider*

1 unit

  AC/DC 200KV

Unnecessary

: necessary item during testing
X: unnecessary during testing
*Filter capacitor: capacitance compensation in order to get smooth voltage output.
 Water resistor: it avoids possible instantaneous high current damaging microampermeter.
 High voltage divider(Kilovoltmeter): Detection output voltage



VII.Standard Accessories:
 
Sr no Description    Qty   Remarks
  1Control unit 10KVA   1 unitStandard  
  2Oil transformer 10KVA/150KV   1 unitStandard
  3Power supply cable   1 unitStandard
  4Connection cables from Controller to Transformer   1 setStandard
  5Calibration report   1 unitStandard
  6Opearting manual   1 unitStandard
  7Discharge rod   1 unitFor buyer's option
  8Micro-ammpmeter   1 unitFor buyer's option
  9Current limit resistor (water resistor)   1 unitFor buyer's option
 10HV filter capacitor   1 unitFor buyer's option
 11High voltage divider   1 unitFor buyer's option

Note:  DC withstand voltage for buyer's option.


VIII.Supplementary notes

1.Series of controller
CapacityInputOutput voltageOutput currentStructureDimensionWeight
(kg)
3kVAAC220VAC0~250V15ABox400mm*300mm*200mm18
5kVA25ABox400mm*300mm*200mm18
10kVA50ABox450mm*340mm*200mm28
15kVAAC380VAC0~450V37.5ABox360mm*450mm*440mm34
20kVA50ADesk610mm*515mm*720mm65
30kVA75ADesk610mm*515mm*820mm86
50kVA125ADesk610mm*515mm*920mm92
 
2.Series of transformer (oil type)
Model
(KVA/KV)
InputOutputLV currentHV currentDimension(mm)Weight
(kg)
3/50AC200V50kV15A60mA320*240*62040
5/5025A100mA360*255*65054
10/5050A200mA410*285*75072
15/50AC400V37.5A300mA440*290*76093
20/5050A400mA450*300*770110
30/5075A600mA480*320*800180
50/50125A1000mA550*350*840244
5/100AC200V100kV25A50mA460*350*110095
10/10050A100mA490*350*1120116
15/100
AC400V
37.5A150mA510*380*1180160
20/10050A200mA530*400*1200182
30/10075A300mA560*430*1250205
50/100125A500mA580*480*1350225
15/150150kV37.5A100mA630*500*1650235
20/15050A133mA640*510*1680240
30/15075A200mA650*540*1710255
50/150125A333mA660*550*1750285
20/200200kV50A100mA740*670*2100300
30/20075A150mA750*680*2200350
50/200125A250mA800*700*2250420






Product Tag:
Related categories:
Scroll to Top