Time test: | 12 channels Open(Close)time Open(Close)same phase no- synchronism Open(Close)phase to phase no-synchronism Close(Open)bounce time(bounce numbers) Internal trigger test range: 0.01ms~10000ms, resolution: 0.01ms, External trigger test range: 0.01ms~200000ms Resolution within 999ms: 0.01ms, 1000-9999ms resolution: 0.1ms. Resolution above 10000ms: 1ms. Accuracy rate within 200ms: 0.05%±1 word |
Velocity test: | Open(Close)velocity Pointed periods of time(travel period or angle period)average speed Range: 1mm Sensor: 0.01~25.00m/s, 0.1mm sensor: 0.001~2.50m/s 360°angle sensor: 1cycle/ 0.25° |
Travel test: | Moving contactor travel Contactor travel (open distance) Overshoot travel or bounce travel (amplitude) Linear sensor:50mm,measuring range: 0-50mm, resolution:0.1mm Linear sensor:100-1000mm(option) Encoder: 360о rotating sensor, measuring range: 0-1000mm, resolution: 0.25о. |
Current & resistance range: | Max. current output 30A, resolution: 0.01A, resistance 1000Ω, resolution: 0.01Ω. |
AC source: | AC 220V ± 10%, 50Hz ± 10% |
DC source: | Output voltage:20~270V continuous adjustment,DC110V≤30A (short time), DC220V≤20A (short time). Power: 4400W. |
External trigger voltage: | AC/DC10-300V, current ≤120A |
Measuring range of isolating switch or energy storage circuit breaker |
|
Working temperature: | -20ºC~+50ºC |
RH: | ≤90% |
Control unit oversize: | 360×260×220mm |
Weight (N.W.) | 5kg (Analyzer) 7kg (Accessories) |