Model | VS-PH030 | VS-PH050 | VS-PH100 | VS-PH150 | VS-PH250 | VS-PH500 |
AC (grid connected) | ||||||
Rated power | 30KW | 50KW | 100KW | 150KW | 250KW | 500KW |
Maximum power | 33KW | 55KW | 110KW | 165KW | 275KW | 550KW |
Rated voltage | 400V | |||||
Rated current | 44A | 73A | 145A | 218A | 362A | 724A |
Voltage range | 320V~460V | |||||
Rated frequency | 50/60Hz | |||||
Frequency range | 45~55/55-65Hz | |||||
THDi grid connection | <3% | |||||
Power factor | 0.99 (lead) ~ 0.99 (lag) | |||||
AC access mode | 3W+N+PE | |||||
Isolation transformer | yes | |||||
AC (off grid) | ||||||
Rated power | 30KW | 50KW | 100KW | 150KW | 250KW | 500KW |
Maximum power | 33KW | 55KW | 110KW | 165KW | 275KW | 550KW |
Rated voltage | 400V | |||||
Rated current | 44A | 73A | 145A | 218A | 362A | 724A |
THDU off grid | ≤ 2% linear | |||||
Rated frequency | 50/60Hz | |||||
Overload capacity | 110% long term / 120% 10min | |||||
Photovoltaic input | ||||||
Maximum input voltage | 1000VDC | |||||
Maximum photovoltaic power | 36kW configurable | 60kW configurable | 120kW configurable | 180kW configurable | 275kW configurable | 550kW configurable |
MPPT voltage range | 520~850VDC | |||||
Battery | ||||||
Rated voltage | 380~460VDC | |||||
Maximum charging power | 36KW | 60KW | 120KW | 180KW | 275KW | 550KW |
General data | ||||||
W * D * H mm | 800*800*2050 | 800*800*2050 | 1200*800*2050 | 1200*800*2050 | 1800*800*2050 | 2800*1050*2050 |
Weight kg | 430 | 620 | 905 | 1250 | 1700 | 3510 |
Working temperature | -25~+55ºC | |||||
Humidity | 0 ~ 95% non condensing | |||||
Degree of protection | IP21 | |||||
Altitude | 6000 m (> 4000 m for derating) | |||||
Cooling mode | Intelligent air cooling | |||||
Communication interface | Ethernet, RS485, can | |||||
Protection function | AC overcurrent / short circuit protection, AC overvoltage / undervoltage protection, AC overfrequency / Underfrequency protection, low / high voltage ride through, anti islanding protection (supporting planned islanding), phase sequence error protection, DC overcurrent / short circuit protection, DC overvoltage / undervoltage protection, DC polarity reverse connection protection, overtemperature protection, power module protection and insulation detection |
Parameter table of energy storage converter(500~1500KW) | ||||||
Project | VSE500PC44SC | VSE630PC44SC | VSE1000PC44SC | VSE1250PC44SC | VSE1500PC44SC | |
DC parameters | Rated voltage | 750 | 750 | 750 | 750 | 750 |
DC voltage range | 500V~900V | 500V~900V | 500V~900V | 500V~900V | 500V~900V | |
Rated power kw | 500 | 630 | 1000 | 1250 | 1500 | |
Maximum power kw | 550 | 693 | 1100 | 1375 | 1650 | |
Rated operating current | 834A | 1051A | 1250A | 1308A | 1365A | |
Maximum operating current | 918A | 1156A | 1375A | 1438A | 1500A | |
AC parameters | Rated power kw | 500 | 630 | 1000 | 1250 | 1500 |
Maximum power kw | 550 | 693 | 1100 | 1375 | 1650 | |
Wiring mode | Three phase three wire / three phase four wire | |||||
Rated voltage | 400Vac | 400Vac | 400Vac | 400Vac | 400Vac | |
Voltage range | 320~440Vac | 320~440Vac | 320~440Vac | 320~440Vac | 320~440Vac | |
Rated current | 722A | 910A | 1070A | 1163A | 1255A | |
Maximum operating current | 795A | 1000A | 1179A | 1281A | 1382A | |
power factor | 0.99(More than half a load) | |||||
Current distortion rate | <3%(Rated power) | |||||
Maximum discharge efficiency | >98.7% | >98.7% | >98.7% | >98.7% | >98.7% | |
DC component | <0.5% | <0.5% | <0.5% | <0.5% | <0.5% | |
Grid connection | support | support | support | support | support | |
Off grid | support | support | support | support | support | |
Low voltage ride through | support | support | support | support | support | |
General parameters | Overload capacity | 110%/long-term,120%/10min | ||||
Width * depth * height mm | 1100*800*2160 | 1100*800*2160 | 1100*800*2160 | 1100*800*2160 | 1906*2378*700 | |
Operating temperature range | -25~55ºC | -25~55ºC | -25~55ºC | -25~55ºC | -25~55ºC | |
altitude | 6000m(>4000mDerating use) | |||||
Cooling mode | Intelligent air cooling | |||||
Degree of protection | IP21 | IP21 | IP21 | IP21 | IP21 | |
communication interface | CAN,485,Ethernet | |||||
Multi machine parallel | have | have | have | have | have | |
Protection function | AC overcurrent / short circuit protection, AC overvoltage / undervoltage protection, AC overfrequency / Underfrequency protection, low / high voltage ride through, anti islanding protection, phase sequence error protection, DC overcurrent / short circuit protection, DC overvoltage / undervoltage protection, DC polarity reverse connection protection, overtemperature protection, power module protection and insulation detection |