Modbus RTU RS485 Port Digital Meter Multi Function Power Meter Three Phase Electrical Instruments

Min.Order: 1
Product origin: Shanghai, China
Infringement complaint: complaintComplaint
US$ 85 ~ 95

Description

 
 
ME437 Three-phase Power Meter
 
Connectivity advantages
MODELME437-SD
Support Extra sensor333mV CT
Rogowski coil
Programmable digital outputRelay
I/O function1*digital output
Power85~265V AC/DC
Storage1GB SD card(Max 4GB)
(save intervals 1mins default)

Feature
 
Specification
ModelME437
Product component typeMultifunction power meter
Poles description3PH4W  3PH3W
1PH2W (L-N); 1PH2W(L-L);1PH3W(L-L-N)
Device applicationPower analysis
Energy meter
Input typeExternal CT(333mV only)
And
External Rogowski coil
Display35 inch TFT screen display
Sampling rate 8k samples per second
Mounting modePanel mounting
Harmonic52th Max
Display characteristics
Feature3.5 Inch TFT screen display 320*480
Mechanical characteristics
Weight350g
DimensionL*W*D:96*96*99mm

Display
Maximum value measured
ParameterRangeResolution
Voltage0.001V
999.9V
999.9kV
999.9MV
0.1
Current999.9A
999.9kA
0.1
Power999.9kW
999.9MW
0.1
Power factor0.9990.001
THD99.9%0.1%
Energy999.9WH
999.9.KWH
999.9MWH
999.9GWH
0.1KWH
0.01MKWH
 
Instantaneous rms Values
VoltageU,UTH2,UTH3,UTH4(Per Phase, AVG)
CurrentI,ITHD2,ITHD3,ITHD4(Per Phase, AVG)
PowerP,FQ,S,PF(Per Phase, SUM)
EnergyEP,EFQ,ES,Freq(Per Phase, SUM)
over 999.9MWh, value reset
UTHD(%)UTHD,THD2,THD3,THD4(Per Phase, AVG)
ITHD(%)ITHD,THD2,THD3,THD4(Per Phase, AVG)
DPFDPFa,DPFb,DPFc, AVG
Update rate
Data acquisition rate400ms
Display update rate0.5s
Calibration
Current Per phase, all
VoltagePer phase, all
Power factorPer phase, all
Energy Reset to "0"  EP,EQ,ES all phase
Pulse Output
Pulse rate changeable by rated currentRated current :100A/500A/1000A/5000A
IMP/KWH   :300/60/30/6

MODBUS RS485
 
Communication
Transmission modeRS485 port,Half duplex
RS485 link 3 wires
Communication protocolMODBUS RTU
Settings
Communication address1 to 247 (default 1)
Baud rate(communication speed)1200 to 57600 baud (default 9600)
ParityEven(default),Old,None 
Data bit8
Stop bit 1

Certificate
Environmental conditions
Operating temperature-25ºC to +55ºC
Storage temperature-40ºC to +85ºC
Humidity rating5 to 95% RH at 50ºC(non-condensing)
Pullution degree2
Overvoltage categoryIII,for distribution systems up to 277/480VAC
Dielectric withstandAs per IEC61010-1, Doubled insulated front panel display
Altitude3000m Max
IP degree of protectionIP20 conforming to IEC 60629
ColourWhite
Contractual warranty12months
EMC
Electrostatic dischargeLevel IV(IEC61000-4-2)
Immunity to radiated fieldsLevel III (IEC61000-4-3)
Immunity to fast transientsLevel IV (IEC61000-4-4)
Immunity to surgeLevel IV (IEC61000-4-5)
Conducted immunityLevel III (IEC61000-4-6)
Immunity to power frequency magnetic fields0.5mT (IEC61000-4-8)
Conducted and radiated emissionsClass B (EN55022 )
Standard compliance
EN 62052-11,EN61557-12,EN 62053-21,EN 62053-22,EN 62053-23,EN 50470-1,EN 50470-3,
EN 61010-1,EN 61010-2,EN 61010-031

Specification
Measurement accuracy
Current 0.5% from 1% to 120%(don't ensure accuracy when <10A)
Rated current 500A(0.5% from 10A to 600A)
3000A(0.5% from 30A to 3600A)
10kA(0.5% from 100A to 12kA)
Rogwoski coil specification100AMRC-16
600AMRC-36
1000AY-FCT-200 or Y-FCT-350 or NRC-100
3000ANRC-150 or Y-FCT-510
6000ANRC-200 or Y-FCT-800
Voltage0.2% from 80V to 400V(or 100 to 500V)
Power factor±0.005 from 10% to 120%
Active/Apparent Power IEC62053-22 Class 0.5
Reactive powerIEC62053-21 Class 2
Frequency0.01% from 45 to 65Hz
Active energy IEC62053-22 Class 0.5s
Reactive energyIEC62053-21 Class 2
Measurement arrange
Measured voltage80V to 400V AC(or 100 to 500V)
Frequency range50/60Hz
Input-current characteristics
Primary current range100A0.5A to 120A
600A0.5A to 720A
1kA1A to 1200A
3kA3A to 3600A
6kA6A to 7200A
Measurement input range 1/225mV-333mV
Permissible overload600mV for 10s/hours
 
Control Power
AC/DC 85 to 265V AC/DC, 3.5W
Output
Digital output 1×digital output(2 ports) from 1pcs relay,rated 24V/800mA, 75mΩmax,
2.5kVrms insulation(controlled by Modbus)
Maximum Switching Power :
0.5A, 125VAC
1A, 30VDC
Wire diameter for terminals
Connections-terminalsScrew terminals 2.5mm2,interval 5.08mm
Alarm
SettingU and I Each phase,AVG
Output formRelay

Data Record
The power meter records data to SD card, the following table lists data record of the power meter.
Record
Record interval1s to 9999s(default 1min)
Record formatcsv
Record capacityMicro SD card 1GB(default)
Store about 1K Bytes data each time
record 2 years (1min & 1GB)
Record dataDate&time,
Voltage(V),UTHD(%),Current(A),ITHD (%),
ITHD3(%),ITHD5(%), ITHD7(%), ITHD11(%), ITHD13(%),
ITHD3(A), ITHD5(A), ITHD7(A), ITHD11(A), ITHD13(A)
Frequency(Hz), PF(power factor),
Active Power(W),Reactive Power(Var),Apparent Power(Va),
Active Energy(Wh),Reactive Energy(Varh),Apparent Energy(Vah)
Current Demand(A),Current Peak Demand(A)&Date
Total Active Power Deamnd(W)
Total Active Power Peak Deamnd(W)&Date
Total Reactive Power Deamnd(W)
Total Reactive Power Peak Deamnd(W)&Date
Total Apparent Power Deamnd(W)
Total Apparent Power Peak Deamnd(W)&Date

Wiring

*:Rogowski coil secondary output voltage can not over 333mV rms.
^:CT must be voltage output,secondary output can not over 333mV rms.
 
3PH4W no VT
3PH3W no VT
3PH3W with VT


 
1PH2W L-N
  1PH2W  L-L

1PH3W L-L-N
 

https://shpytech.en.made-in-china.com/product/RZsfXICAfYVb/China-High-Voltage-D-Src-36kv-AC-Current-Transducerrogowski-Current-Transducer.html

https://shpytech.en.made-in-china.com/product/rONaSMZGLYVc/China-Nrc-Promotion-Rogowski-Coil-Current-Transducer-Rogowski-Transducer.html

https://shpytech.en.made-in-china.com/product/qZvAEMsJHUWm/China-STP-Built-in-Integrator-Selectable-Rogowski-Coilflexible-AC-Current-Probes.html

https://shpytech.en.made-in-china.com/product/gdSTRYPJOUcW/China-Remote-Handheld-Digital-Power-Quality-Analyzer-with-TFT-Display.html

https://shpytech.en.made-in-china.com/product/mdOtRPWuHphc/China-A05-High-Quality-Shield-Aluminium-Alloy-Enclosure-5A-Output-Rogowski-Coil-Converter.html

 





Product Tag:
Related categories:
Scroll to Top