Description
OVERVIEW
HFC-227ea fire extinguishing agent is colorless, odorless, non-conductive, and has zero depletion potential (ODP) on the ozone layer, which meets environmental protection requirements. HFC-227ea fire extinguishing agent has the advantages of high fire extinguishing efficiency, no pollution to equipment, good electrical insulation, and rapid fire extinguishing. It is an ideal substitute for halogenated alkane fire extinguishing agents.
HFC-227ea automatic fire extinguishing system has three control modes: automatic, electrical manual and mechanical emergency manual. The system is mainly composed of: automatic alarm and fire extinguishing control system, fire extinguishing agent cylinder kit, actuating cylinder kit, release device, selection valve, check valve, nozzle, piping system and other main components. According to the requirements of use, it can be composed of unit independent systems, combined distribution systems and other forms to implement single-zone and multi-zone fire protection.
It is mainly applicable to the fire protection of key units such as electronic computer rooms, telecommunications centers, underground projects, offshore oil production platforms, libraries, archives, treasure stores, power distribution rooms, etc.
CABINET TYPE
PIPELINE TYPE
APPLICATIONS
The gas (HFC-227ea) filled in the pipe network type heptafluoropropane fire extinguishing device has good clean performance, network has low working pressure, small storage space, does not destroy the ozone layer, meets environmental protection requirements, and has characteristics of colorless, odorless, non-conductive, no secondary pollution, and fast and efficient fire extinguishing. It is an ideal substitute for halon fire extinguishing agent at this stage It is used to extinguish all types of fires A, B, and C.
Especially for some electrical and electronic equipment, communication facilities, flammable liquids and gases, and for other fire protection of high-value property, the device has no residue after spraying, has low toxicity of the agent, and can be used safely in places with people. The advantages are more prominent for places where people often work.
- Bank Vaults
- Libraries
- Rare Book Stores
- Electronic Data Processing
- Telephone Exchange Studios
- Communication Centre
- Transformer and Switch Rooms
- Control Rooms
- Test Laboratories
- Flammable Liquid Stores
FEATURES - Low concentration of HFC-227ea required means less visual obscurity and minimal risk to personnel.
- Small quantity of agent discharged minimises over pressurisation of the protection area.
- Max Safety for personnel due to low toxicity.
- High effective with 10 second discharge time when used with automatic detection.
- Prevent re-ignition as long as concentration levels are maintained.
- Two kinds of working pressure system are available,(25 bar / 360 psi and 42 bar / 600 psi).
Agent Cylinder
The fire extinguishing agent cylinder filled by JUNMO with HFC-227ea, and super-pressurised with dry nitrogen to 25 bar @ 21ºC (360 psi @ 70°F) and 42 bar @ 21ºC (600 psi @ 70°F).
JUNMO Agent Cylinders sharing the same manifold shall be equal in size and fill density. Cylinders are finished in red and are available in various sizes.
Volume | Fill Capacity (kg) | Outlet Size | Height | Diameter | Empty Weight |
Minimum | Maximum |
40L | 19.2 | 44.8 | 33/49 | 830 | 324 | 42.0 |
50L | 24.0 | 56.0 | 33/49 | 950 | 324 | 43.6 |
60L | 28.8 | 67.2 | 33/49 | 1100 | 324 | 49.9 |
70L | 33.6 | 78.4 | 49 | 1250 | 324 | 56.2 |
80L | 38.4 | 89.6 | 49 | 1400 | 324 | 62.6 |
90L | 43.2 | 100.8 | 49 | 1200 | 406 | 68.4 |
100L | 48.0 | 112.0 | 49 | 1310 | 406 | 72.4 |
120L | 57.6 | 134.4 | 49 | 1245 | 406 | 96.2 |
150L | 72.0 | 168.0 | 49 | 1495 | 406 | 113.1 |
180L | 86.4 | 201.6 | 49 | 1745 | 462 | 130.2 |
PIPELINE TYPE SYSTEM DATA |
Model | QMQ4.2/90N-JM | QMQ4.2/120N-JM | QMQ4.2/150N-JM |
Cylinder Capacity (L) | 90 | 120 | 150 |
Max. Working Pressure (MPa) | 5.3 |
Storage Pressure (MPa) | 4.2 |
Working Temperature Range | 0~50°C (System room); -10°C (Min Temp. in protection area) |
Charging Rate (Kg/L) | ≤0.95 |
Air actuating Pressure (MPa) | 6 |
Operating Voltage (V) | AC220 |
Back-Up Power (V) | DC24 |
Discharging Time (S) | ≤10 |
System Startup Method | Automatic / manual / emergency operation |
Standard | GB16670-2006 |
OTHER SIZES CYLINDER AVAILABLE |
CABINET TYPE SYSTEM DATA |
Model | GQQ40/2.5-JM | GQQ70/2.5-JM | GQQ90/2.5-JM | GQQ120/2.5-JM | GQQ150/2.5-JM |
Cylinder Capacity (L) | 40 | 70 | 90 | 120 | 150 |
Max. Working Pressure (MPa) | 4.2 |
Storage Pressure (MPa) | 2.5 |
Working Temperature Range | 0~50°C (System room) |
Charging Rate (Kg/L) | ≤1.15 |
Air actuating Pressure (MPa) | 6 |
Operating Voltage (V) | AC220 |
Back-Up Power (V) | DC24 |
Discharging Time (S) | ≤10 |
System Startup Method | Automatic / manual |
Standard | GB16670-2006 |
OTHER SIZES CYLINDER AVAILABLE |