Brand | IDEALPLUSING | |
Model | IPS-DTA6000-48 | |
Rate Capacity(KVA) | 6000VA | |
Rate power(W) | 4800W | |
DC Input | Rate input voltage | 48VDC |
Rate input Current | 117A | |
Shut down voltage range | 40~58.8VDC | |
Start-up voltage range | 42~57VDC | |
Reflect noise current | ≤10% | |
AC Input | Allow bypass voltage | 220VAC |
Bypass switch time (ms) | ≤5ms | |
AC Output | Rated capacity (VA) | 6000VA |
Rated output power (W) | 4800W | |
output voltage | 220VAC | |
Output voltage precision | 220±10VAC | |
Output frequency precision | 50±0.1% Or 60±0.1% HZ | |
Waveform | Pure sine wave | |
Total harmonic distortion | ≤3% (linear load) (THD) | |
Dynamic response time | 5% (load 0←→100%) | |
Power factor (PF) | 0.8 | |
Overload capacity | 100%-120% 60s121%-150% 10s | |
Inversion efficiency (80% resistive load) | ≥85% | |
By-pass conversion time (ms) | ≤5ms | |
Operating environment | Dielectric strength (input and output) | 1500VAC, 1 minute |
Noise (1m) | ≤65dB | |
Operating environment temperature | -20ºC~+50ºC | |
Humidity | 0~90%, no moisture condensation | |
Operating altitude (m) | ≤2000 | |
Indication | LCD display | Input and output voltage, frequency, output current, temperature, percentage, etc. |
inverter status | Normal mains, normal inversion, battery under-voltage and output overload | |
Mechanical size | Standard rack (Depth * Width * Height) (mm) | 482*368*88(MM), 15KG |
Protection function | Input under-voltage and over-voltage, output overload and short circuit protections, etc. |
NO | Model | Size(MM) | Net Weight(KG) | Input Voltage(V) | Output Voltage(V) | Output Capacity(VA) | Power (W) |
#1 | IPS-DTA500-24 | 2U482*88*335mm | 8KG | 24VDC | 220VAC | 500VA | 400W |
#2 | IPS-DTA1000-24 | 2U482*88*335mm | 8KG | 24VDC | 220VAC | 1000VA | 800W |
#3 | IPS-DTA2000-24 | 2U482*88*335mm | 10KG | 24VDC | 220VAC | 2000VA | 1600W |
#4 | IPS-DTA3000-24 | 2U482*88*368mm | 12KG | 24VDC | 220VAC | 3000VA | 2400W |
#5 | IPS-DTA1000-48 | 2U482*88*335mm | 9KG | 48VDC | 220VAC | 1000VA | 800W |
#6 | IPS-DTA2000-48 | 2U482*88*335mm | 10KG | 48VDC | 220VAC | 2000VA | 1600W |
#7 | IPS-DTA3000-48 | 2U482*88*368mm | 12KG | 48VDC | 220VAC | 3000VA | 2400W |
#8 | IPS-DTA4000-48 | 2U482*88*368mm | 14KG | 48VDC | 220VAC | 4000VA | 3200W |
#9 | IPS-DTA5000-48 | 2U482*88*368mm | 14KG | 48VDC | 220VAC | 5000VA | 4000W |
#10 | IPS-DTA6000-48 | 2U482*88*368mm | 15KG | 48VDC | 220VAC | 6000VA | 4800W |
#11 | IPS-DTA1000-110 | 2U482*88*335mm | 9KG | 110VDC | 220VAC | 1000VA | 800W |
#12 | IPS-DTA2000-110 | 2U482*88*335mm | 10KG | 110VDC | 220VAC | 2000VA | 1600W |
#13 | IPS-DTA3000-110 | 2U482*88*368mm | 12KG | 110VDC | 220VAC | 3000VA | 2400W |
#14 | IPS-DTA4000-110 | 2U482*88*368mm | 14KG | 110VDC | 220VAC | 4000VA | 3200W |
#15 | IPS-DTA5000-110 | 2U482*88*368mm | 14KG | 110VDC | 220VAC | 5000VA | 4000W |
#16 | IPS-DTA6000-110 | 2U482*88*368mm | 15KG | 110VDC | 220VAC | 6000VA | 4800W |
#17 | IPS-DTA1000-220 | 2U482*88*335mm | 9KG | 220VDC | 220VAC | 1000VA | 800W |
#18 | IPS-DTA2000-220 | 2U482*88*335mm | 10KG | 220VDC | 220VAC | 2000VA | 1600W |
#19 | IPS-DTA3000-220 | 2U482*88*368mm | 12KG | 220VDC | 220VAC | 3000VA | 2400W |
#20 | IPS-DTA4000-220 | 2U482*88*368mm | 14KG | 220VDC | 220VAC | 4000VA | 3200W |
#21 | IPS-DTA5000-220 | 2U482*88*368mm | 14KG | 220VDC | 220VAC | 5000VA | 4000W |
#22 | IPS-DTA6000-220 | 2U482*88*368mm | 15KG | 220VDC | 220VAC | 6000VA | 4800W |