100mva Outdoor Transformer Oil Immersed, High Voltage Onaf Ynd11 on Tap Changer

Min.Order: 1
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ -1

Description
100MVA Outdoor Transformer Oil immersed, High Voltage 13.8KV to 138KV ONAF YNd11 On Tap Changer
 

1.Product introduction

Three-phase high-voltage power  transformers can be widely used in industry, such as start spot welding machine, automatic welding machine, butt welding machine, straightening machine, steel wire rolling machine, diffusion welding machine, seam welding, roll welding, touch welding, row welding machine etc.

 

 

2. Normal operating conditions

Three-phase high-voltage power transformer should be able to work normally under the following conditions:

a) Altitude: not more than 1000m;

b) Ambient temperature: -15 ºC ~ + 40 ºC

c) The relative humidity of the air does not exceed 95% (at + 25 ºC);

d) In a gas or steam environment without damage to insulation;

e) Used in explosive environment without methane coal dust.



3. Product parameters
 

ItemDescirptionOffered
1General information
1.1SupplierMarkevina China
1.2Place of manufactureChina
2Type of transformerCore, Outdoor, Oil immersed
3Continuous ratings Capacitor33.333MVA
4Phase1
5Cooling  TypeONAF
6Rated voltage on principal tapping138/13.8kV
7Rated frequency60Hz
8Vector Group(After three single-phase transformers are connected externally)YNd11
9Tap-changers
9.1TypeOLTC
9.2MakerGuizhou Changzheng
9.3ModelZM Model
9.4Preclse electrical location of tappingsHV
9.5Tapping range of HV/LV ratio % of the ratio on the principal tapping
9.5.1Max10%
9.5.2Min10%
9.6Number of steps17 steps
9.7Size of steps1.25%
10Ohmic impedance at 75ºC and rated frequency based on maximum rated power of HV winding
10.1On principal tapping10.50%
10.2On extreme plus tapping11%
10.3On extreme minus tapping10%
11Temperature rises
11.1Top oil (thermometer) 55K
11.2Winding(by resistance)65K
12No-load loss on principal tapping at ratings32kW
13load loss at ratings108kW
14Impulse withstand test voltage for(1.2/50us)
14.1HV650kV(peak)
14.2LV95kV(peak)
14.3HV of Netural point325kV
15Sixty-second, power-frequency withstand test voltage 
15.1HV275kV(rms)
15.2LV28kV(rms)
15.3HV of Netural point140kV
16Main terminal bushings 
16.1Impulse withstand test voltage at sea level(1.2/50us)
16.1.1HV650(peak)
16.1.2LV125(peak)
16.1.3HV of Netural point325kV
16.2Sixty-second,power-frequency withstand test voltage to earth
16.2.1HV275kV(rms)
16.2.2LV50kV(rms)
16.2.3HV of Netural point140kV
17Approx. Mass 
17.1Core &coils21700kg
17.2Mass of oil10400kg
17.3Total mass48600kg
17.4Shipping mass for heaviest part39500kg
18Filling medium for transportOil
19Overall dimensions of heaviest part
Length*Width*Height4500*2200*3200
20Overall dimensions of complete transformer 
Length*Width*Height4700*5300*5700


 