3 Phase Multi-Function Electric LCD Display 3 Phase 4 Wire Digital Power Meter with RS485 Modbus

Min.Order: 10
Product origin: Chengdu, Sichuan, China
Infringement complaint: complaintComplaint
US$ -1

Description
FEATURES

1
Segment LCD(white backlight)
2
Available to measure voltage/current/active power /reactive power /frequency/power factor, etc, total 28 units.
3
RS485 communication,Modbus RTU procotol
4
Active/reactive Kwh/ four-quadrant Kvarh measured function, with pulse output port.
 
5
4 loop DI and 2 loop alarm output, input and output completely isolated, with remote control and telecommand functions.
6
Optional 1 loop 4 ~ 20mA analog output function.
7
3 phase voltage/current subharmonic measurement (2 ~ 32)
8
8 periods, 4 kinds of rate statistics function. (multi-rate function)

ModelAnalog outputAlarm outputDIRS485Multi-rateHarmonicInput range
DW9L-RC38No2 loop4 loop1 loopYesYes10~480v(L-L)
0.02~6A
DW9L-IRC384~20m2 loop4 loop1 loopYesYes
Product Parameters
Input signal
Input voltage
10~480V(L-L) each phase power consumption <1VA
Voltage impedance
≥300KΩ
Input current
0.02~6A        each phase power consumption <0.4VA
Current impedance
<20mΩ
Rated frequency
50Hz,60Hz (To ensure the accuracy, pls advise the specific frequency range, if 60Hz~500Hz is needed.)
Accuracy
Active energy: 0.5S class Reactive energy: 2 class Voltage/current: 0.2%FS
Measured range
Current: 0.02A~6A         Voltage: Phase voltage L-N:10~277V, wire voltage L-L: 10~480V
Electr-ical

para-meter
Relay capacity
AC 250V 5A DC24V 5A (Resistive load)
Analog output
DC 4~20mA Load<500Ω
Display device
Industrial segment LCD display        Clock accuracy: <0.5 second per day
DI
Dry contact input        Input voltage
Communication
Communication port
RS485 port(Modbus RTU procotol,and DL/645 procotola) Baud trate: 4.8kbps /9.6kbps  (19.2kbps can be ordered)
Pulse output
1 loop energy pulse output (PhotoMOS relay) Pulse constant 9000imp/kwh
EMC
ESD
IEC/EN61000-4-2 Air±8KV/Contact ±6KV perf.Criteria B
Pulse train
IEC/EN61000-4-4 ±4KV                 perf.Criteria B
Frequency drop
IEC/EN61000-4-11 0%-70%           perf.Criteria B
Lightning surge
IEC/EN61000-4-5 ±2KV/±4KV      perf.Criteria B
Radiated emission
CISPR22/EN55022 CLASS B
Conducted emission
CISPR22/EN55022 CLASS B
Radiated immunity
IEC/EN61000-4-3 10V/M perf.Criteria A
 
Conducted immunity
IEC/EN61000-4-6 10 Vr.m.s perf.Criteria A
Power frequency immunity
IEC/EN61000-4-8 10A/M perf.Criteria A
Environment
Working environment
Temperature range: 0ºC~50ºC Limit condition-10ºC~55ºC Humidity range: 5~90%R.H(no condensation)
Storage temperature
-25ºC~60ºC
Shell
specifications 
Material
VO class flame retardant, PC+ABS, PC panel       Protection level IP65(front panel)
Insulation resistance: input/output/power against shell>100MΩ
Shockproof
10~57Hz (XYZ direction 2G/30 minutes)
Power
Power voltage
AC/DC 100~240V 50/60Hz   Power consumption<7VA
 
Safety
Withstand voltagew
Input signal and power 2000 VAC,input and output 2000 VAC,power and analog output, RS485 port,pulse output port≥AC 2000V
Weight
About 0.6kg