(1) Can measure the system's positive to ground voltage, system voltage, and voltage monitoring range 0-300V;
(2) It can measure the insulation impedance of the system to ground, detect the size of the balance bridge, and have a detection range of 0-999.9K Ω;
(3) It can measure the AC voltage component that enters the DC system, with a measurement range of 0-280V;
(4) It can measure and display the distributed capacitance of the system in real-time.
(5) It can detect various ring network faults in two bus sections, including positive and negative rings, bipolar rings, and heteropolar rings, and can locate the ring network fault point through waveform display and directional display;
(6) The device can achieve the detection and positioning of high resistance ring network faults through amplitude modulation, frequency modulation, current waveform selection, etc.
(7) It can measure the insulation impedance of each branch to ground, and locate insulation fault points through waveform display and direction display;
(8) Equipped with spectrum analysis function for current changes based on fast FFT transformation technology, efficient sampling, and improved detection accuracy;
(9) The device can be used as a high-precision ammeter, with a measurement resolution of up to 0.01mA;
(10) The equipment can automatically identify the system voltage level and determine the category of ring network faults;
Working power supply | DC40V-300V |
DC voltage measurement | |
DC voltage measurement range | 0-300V |
DC voltage measurement resolution | 0.1V |
DC voltage measurement accuracy | 0.20% |
AC voltage measurement | |
Measurement of AC and DC surge voltage | 0-280v |
AC voltage measurement resolution | 0.1V |
AC voltage measurement accuracy | 0.50% |
Insulation resistance measurement | |
Insulation resistance measurement range | 0-999.9K Ω |
Insulation resistance measurement resolution | 0.1K Ω |
Insulation resistance measurement accuracy | ≤ ± 5% |
Detection bridge amplitude adjustment range | 0mA, 0.25mA, 0.5mA, 1mA, 2mA |
Detection ring network resistance range | within 50K Ω |
Measurement of system distributed capacitance | |
System distributed capacitance measurement range | 0-999.9uF |
System to ground capacitance measurement | 0-1000k Ω |
Selection of detection waveform type | sine wave, square wave |
Working mode | forced signal start, automatic signal start |
Display medium and resolution | TFT, 320x240 |
Technical parameters of the detector
Insulation resistance measurement | |
Insulation resistance measurement range | 0-500K Ω |
Insulation resistance measurement resolution | 0.1K Ω |
Insulation resistance measurement accuracy | ≤ ± 10% |
Spectrum analysis range | |
Number of spectral analysis channels | 1 |
Spectrum analysis frequency range | 0.125-12.5Hz |
Frequency resolution | 0.125Hz |
Current waveform display cycle | 8 seconds; |
Detectable feeder current range | 0-2A; |
Current measurement range | -100-+100mA; |
Current measurement resolution | 0.01 mA |
Display medium and resolution | TFT, 320x240 |