Portable Current Transformer CT PT Testing Equipment

Min.Order: 1
Product origin: Chongqing, China
Infringement complaint: complaintComplaint
US$ 8000 ~ 9000

Description
CPT-III Current Transformer CT PT Testing Equipment CT PT Volt-Ampere Characteristic Analyzer
Product Description
CPT-III CT PT Volt-Ampere Characteristic Analyzer is used to measure all kinds of current transformer and voltage transformer.

It can calculate the ratio errors and phase angle errors of current transformer and voltage transformer at rated burden and working burden in one test.

CPT-III CT PT Volt-Ampere Characteristic Analyzer can automatically evaluate the test results according to the selected standard to determine whether the transformer is qualified.

 

Product Parameters

Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
Power supply: AC220V±10%, 50/60Hz±10%
Voltage output: 0.1~180V (AC)
Current output: 0.001~5A(RMS)
Power output: 500VA
Maximum knee voltage measurement: 45KV
PT ratio error measurement: typical error <0.05%, maximum error<0.1%
PT phase angle measurement: maximum error < 3min
Memory capacity: >1000 groups test results
Working condition: temperature: -10ºC~50ºC, humidty: ≤90%
Size: 485mm * 356mm * 183mm, weight: <15kg

Test ParametersRangeErrorResolution
Current0~10A (automatically change range in 0.1/0.4/2/10A)<±0.1%+0.01%FS/
Voltage0~200V (automatically change
range in 1V/10V/70V/200V)
<±0.1%+0.01%FS/
Turns Ratio1~5000<0.05%/
5000~35000<0.1%/
Phase/±2minResolution: 0.01min
Winding Resistance0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)<0.2%RDG+0.02%FSMax. resolution: 0.1mΩ
Temperature-50~100 Celsius degree<3 Celsius degree/
CT Secondary Burden0~160ohm
(automatically change range in 2ohm/20ohm/80ohm/160ohm)
<0.2%RDG+0.02%FSMax. resolution: 0.001ohm
PT Secondary Burden0~80kohm (automatically change
range in 800ohm/8kohm/80kohm)
<0.2%RDG+0.02%FSMax. resolution: 0.1ohm
PT Ratio1~10000<0.1%/
10000~35000<0.2%/
 
Features

1. Panel

2. Software
Functions of test software:
Make evaluation for test results according to selected standards.
Make word report for test result.
Make word reports one time for multi-group test records on the PC.
Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test.
Compare excitation curves with saved excitation curves in the same window.

3. The whole set
4. The Main tester

5. Accessories

NameQty.Description
3M mask cable2pcsTest cable for power out and CT secondary connection
10M mask cable1pcTest cable for CT primary connection
Grounding cable1pc 
Big test pliers2pcsOne red and one black
Test gasket4pcsTwo red and two black
Test pin4pcsTwo red and two black
Test pliers12pcsThree red and nine black
Short connection cable1pcIncluding six connection terminals
3A fuse3pcs 
Power cable1pc 
Accessories bag1pc 
Production disk1pcInclude  Analysis  application  and  user manual
User manual2pcs 




Product Tag:
Related categories:
Scroll to Top