Manufacturer | Dynamic Energy | |
Genset model | 600GFZ1-PwW-TEM2 | |
Engine model | 12V190ZL | |
Alternator model | 1FC6 457-6LA42-Z | |
Breaker panel model | GCBP1 | |
Field control panel | FCP1 | |
Local control panel | LCP1 | |
Rated power | kW | 600 |
Rated voltage | V | 400 |
Rated current | A | 1082 |
Rated power factor | cosφ | 0.8 (lagging) |
Frequency | HZ | 50 |
Fuel gas consumption | MJ/(kW·h) | 9.4 |
Lubricant consumption | g/(kW·h) | ≤0.8 |
Electrical efficiency | % | 38 |
Start-up method | DC 24V Electric motor | |
Start-up control | Manual/Automatic | |
Wiring method | 3 phase 3 line/3 phase 4 line | |
Stable speed droop | % | ≤5 |
Cooling method | Closed loop, with fan radiator | |
Exhaust back pressure max. | 6 kPa | |
Noise level | 106 db @ 1 meter away from the genset 34 db @ 1 meter away from engine muffler | |
Genset vibration | ≤7.2mm/s | |
Coupling between engine and alternator | Elastic coupling | |
Dimension (L×B×H) | mm | 5504X2000X2870 |
Weight | kg | 14650 |
Major over period | hour | 30000 |