Manufacturer | | Dynamic Energy |
Genset model | | 400GFZ1-PWT-ESM3 |
Engine model | | T12V190 |
Alternator model | | 1FC6 406-6LA72 |
Breaker panel model | | GCBP |
Field control panel | | FCP1-500Z |
Local control panel (Optional) | | LCP1-3GS |
Rated power | kW | 400 |
Rated current | A | 866 |
Rated voltage | V | 480 |
Rated power factor | cosφ | 0.8 (lagging) |
Frequency | HZ | 60 |
Fuel gas consumption | MJ/(kW·h) | 11.5 |
Lubricant consumption | g/(kW·h) | ≤1.0 |
Electrical efficiency | % | 31 |
Start-up method | | DC 24V Electric motor |
Start-up control | | Manual/Automatic |
Wiring method | | 3 phase 3 line/3 phase 4 line |
Stable speed droop | % | ≤5 |
Cooling method | | Closed loop, with fan radiator |
Exhaust back pressure max. | | 6 kPa |
Noise level | | 105 db @ 1 meter away from the genset |
Genset vibration | | ≤7.2mm/s |
Coupling between engine and alternator | | Elastic coupling |
Dimension (L×B×H) | mm | 5433X1970X2700 |
Weight | kg | 11200 |
Major component/system supplier & description: |
Overall genset management | Dynamic TEM3 control system |
Air/ fuel ratio control | IMPCO mechanical mixer or Varifuel electronic venturi mixer |
Speed governing system (digital) | Woodward / Heinzmann |
Ignition (digital) | Altronic Magneto Ignition System/Altronic dignital ignition system |
Intelligent circuit breaker | Changshu Switchgear/Tianshui 213 |