LFP LiFePO4 Ess Energy Storage Lithium Ion Battery Solar Energy 24V 48V 51.2V 50ah 100ah 150ah 200ah with CE, Un 38.3

Min.Order: 1
Product origin: Beijing, China
Infringement complaint: complaintComplaint
US$ 500 ~ 590

Description
Battery Pack Performance Specifications 
 Rated voltage51.2V 
 
 Rated capacity100Ah 
 Rated energy5120Wh 
 maximum continuous5kW 
 power
 Maximum number oparallel connections  
 RS485: 15 
 Series connectionProhibit 
 BMS Model16S100A 
  Over-charge protection;Over-discharge 
Electrical CharacteristicsBMS Functionprotection;Over-current protection;short 
  circuit protection;Temperature protection 
  and balance function 
 Heating FunctionOptional 
 CommunicationRS232;RS485;CAN  (Optional) 
 Cycle life2000 cycles  (0.5Ccharge and discharge, 
 80%DOD ,60%EOL ,25C) 
 Equalizing voltage56V 
 Float voltage55.2V 
 Standard charging20A/1000W 
Charging characteristicscurrent/power
 Max charging50A/2500W 
 current/power
 Standard discharging current/power20A/1000W 
 Max discharging100A/5000W 
Discharging characteristicscurrent/power
 Discharge end of voltage43.2V 
 Size  (W×D×Hmm440×470×156  (19inch 3.5U) 
 Shell materialmetal housing 
Mechanical characteristicsWeightAbout 50Kg 
 Waterproof RatingIP20(indoor use ) 
TemperatureCharge temperature0C to 50C 
characteristicsDischarge temperature-20C to 55C 
 Best performance10C to 40C 
temperature
 Storage temperature≤ 35C,50%SOC ,6 months 
BMS parameters 
No  The    reference standard    (the
ItemDetailset value is subject to the
  actual set value)
  Cell overcharge alarm voltage3.50~3.90V
 OverchargeOverall overcharge alarm voltage56.40V~57.60V
1protectionCell overcharge protection voltage3.50~3.90V
  Overall overcharge protection voltage56.40V~57.60V
  Cell over discharge alarm voltage2.0V~2.90V
 Over discharge protectionOverall over discharge alarm voltage36.00V~48.00V
2 Over discharge protection voltage2.0V~2.90V
  Overall over discharge protection voltage36.00V~48.00V
  Protection conditionsExternal circuit short circuit
  
  
 Short    circuit protectionDelay time1mS
3  Cut loadIf a short circuit is
   triggered multiple timesit is
  Release conditionlocked into a protected state.
   After the user needs to check
   the external circuit, reset the
   BMS and release the protection.
  Battery high temperature warning35C~65C
 Temperature protectionBattery high temperature protection35C~65C
4 Battery low temperature warning-20C~0C
  Battery low temperature protection-20C~0C
  Balance turn-on voltage45V±0 02V
5Charge balanceBalance turn-on voltage difference20mV
  Balance current85mA±20mA
6CommunicationRS232/RS485Default baud rate is 9600bit/S
 PowerCircuit consumes current while working50mA
7consumptionSleep mode consumes current300 μA
Product Tag:
Related categories:
Scroll to Top