Sf6 Gas Insulated Load Break Switch Switchgear 12kv 22kv Ring Main Unit (rmu) Switchgear Indoor Power Substation /Lbs Breaker/Load Break Switch

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 5

Description
Product Description

1.Brief Introduction

   XGN15-12(L)/T630-25 0r XGN15-12(L . R)/T100-31.5 Cubicle fixed AC metal enclosed switchgear is mainly used for looped network power supply or biradial power supply of electric power system with 3-phase ,AC 50Hz and rated voltage 10KV. It also can be used for terminal power supply as the control device of electric energy and protection device of utilization equipment. More over, it also can be suitable for this switchgear
to be installed in the box substation, especially compact box substation.


2.Service Environmental Condition
 Altitude: .< lOOOm
Ambient temperature: -25aC ~ +400C
Relative humidity: The daily average value is not more than 95% and the monthly mean value is not more than 90%.
The surrounding air shall not be polluted by corrosive gas and flammable gas as well as water vapor and so on obviously.
. No location of recurrent strenuous vibration


3.Main structure of switch cabinet
It consists of such parts as bus compartment, 3-position load switch compartment (or circuit breaker compartment), cable compartment, actuator, interlocking mechanism and low-voltage control room as well as measuring circuit or metering circuit and so on. Every compartment is separated by the steel plate so that the fault part avoids affecting the adjacent compartment. It conforms to the GB3906 and IEC298 standard and so on.

. Bus compartment
The bus compartment is arranged on the upper part of cabinet body. The main buses are connected together in the bus compartment and they passes through the whole array of switch cabinet. The arrangement of bus is horizontal and it can be spread out conveniently.

. Load switch compartment
There is a 3-position load switch installed in the switch compartment. The casing of load switch is poured by the epoxy resin. The Sf6 gas is refilled as the arc-extinguishing and insulating medium in the compartment. There are 2 transparent plastic end cover by means of thermal forming installed at the leading end of operating shaft. The contact state can be observed through it. The SF6 gas density gauge or gas density apparatus with alarm contact is installed in the switch compartment according to the client requirement.

. Cable compartment
The cable compartment is mainly used for cable connection. For the connection of single-core cable, the simplest non-shielded cable head is used. At same time, there are such elements as lightning arrester, current transformer and lower grounding switch and so on also can be contained in the enough room. There are observation window and safety interlocking device in the cabinet door as per the standard design. The back plate in the cable compartment is equipped with the sealing cover and appropriate size of cable clamp with support. The frame in front of door at the back plate in the cable compartment can be dismounted for easy cable installation.

. Operating mechanism , interlocking mechanism and low-voltage control room
The low-voltage room with interlocking functions as the screen control at same time. The low-voltage room is equipped with the spring actuator with position indicator and mechanical interlocking device. The auxiliary contact, tripping coil, emergency tripping mechanism, capacitor-type charged display device, key lock and electrical operation device are installed in the low-voltage room. At same time, the control circuit and metering instrument as well as protection relay also can be installed in the spacing of low-voltage room.
There are 2 same low-voltage rooms installed in the 750mm wide cabinet and more accessories can be installed in this size of cabinet.

 
Product Parameters

 

 4.The main technical parameters 
NO.ItemUnitTechnical parameters
XGN15-12(F)XGN15-12(F,R)
1Rated  voltageKV12
2Rated  FrequencyHz50
3
 
Rated insulation level1 min power frequency withstand voltageKvTo-Grounding and phase -to-phase42;Isolating distance48
Lighting impulse withstand voltage(peak)kvTo-Ground and phase-to-phase 75;
Isolating distance85
4Rated current of main busA630
6Rated  currentA630125
7Rated closed loop breaking currentA630 
8Rated charging breaking currentA10
9Rated  transfer currentA 1700
10Breaking no-load transformer capacityKVA1600
11Rated making current(peak)KA63 
12Rated short-time withstand currentKA25 
13Rated peak withstand currentKA63 
14Rated short-circuit breaking currentKA  
15Peak withstand current of ground circuit(prospective)KA6331.3(Prospective)
16Short-time withstand current of grounding circuitKA25
17Fuse model  SLAJ
18Rated voltage of auxiliary circuitVDC220 110 AC220 110
19IP Code IP3X

20

Mechanical life
Load switch (times)Times5000
Earthing switch(times)Times2000

5.Ring main unit configuration table
 NameDescriptionUnit
Load break switchFL+C2:D7+C2:D12N36- 24/630-20Load break switch for Two positions, no earthing
with Gas-pressure meter
Set
FL(R)N36- 12D/630-20Load break switch for Three positions
with Gas-pressure meter
Set
FLN36- 24/630-20 Load break switch for Two positions, no earthing
with Gas-pressure meter
Set
FL(R)N36- 24D/630-20Load break switch for Three positions
with Gas-pressure meter
Set
FL(R)N36- 35/630-20 Load break switch for Two positions, no earthing
with Gas-pressure meter
Set
FL(R)N36- 35D/630-20Load break switch for Three positions
with Gas-pressure meter
Set
Operating mechanismOrganization for in lineManual operation for K type(No button) (not suitable for fuses)Set
Organization for in and out lineManual operation for A type(with button)Set
Organization for in and out lineElectric operation AC220VSet
Organization for in lineManual for closing and electric for OpeningSet
Only for 12kv 24kv (outgoing line)
35kv load break switch is protected by
microcomputer
Fuse holders
 
Top and bottom fuse holder 6pcs totallySet
Fuse(See the below)Set
Interlock systemDown door interlockThe interlock for down door
 
Set
Trip device(Including the trip system and trip  interlock,work together with fuse holders)
 
 Trip system 
 
Set
Trip interlockSet
Earthing interlock
 
 500 #/375# earthing componentsSet
 Sensors3pcs as one setSet
 Voltage IndicatorL-6Set

The general selection principle of rated current of the fuse element selected by transformer capacity is shown in table 

Transformer capacity (kVA)
100125160200250300
315
400500630750
800
10001250
Rated current of fuse element (A)16202531.540506380100

6. According to the actual use, the SF6 RMU (SM6) cabinet has the following devices.
SF6 (SM6) Switchgear cabinet types
NO.NameSpecificationUnitQty NO.NameSpecificationUnitQty
 XGN15-12 Lifttlig Switchgear Set1  XGN15-12 Outline Switchgear Set1
1Lighting ArresterHY5WS 17/50Set1 1SF6 load break swithFRLN36-12D/125-31.5Set1
2Voltage displayL-6Set1 2Operating mechanismManual for closing
and Electric for Open
  
3Electromagnetic lockDSN-YSet1 3Gas meter Set1
4Sheet metal375*916*1635Set1 4Outline Electromagnetic lock375#Set1
     5Lighting ArresterHY5WS 17/50Set1
NO.NameSpecificationUnitQty 6SensorCG5-10 140mmSet1
  XGN15-12 Mertering SwitchgearSet1 7Voltage displayL-6Set1
1SensorCG5-10 140mmSet1 8Fuse10A-63ASet1
2Voltage displayDXN-QSet1 9Sheet metal375*1000*1635Set1
3Electromagnetic lockDSN-Z 220VSet1     
4Sheet metal750*916*1635Set1 NO.NameSpecificationUnitQty
       XGN15-12 Outline SwitchgearSet1
NO.NameSpecificationUnitQty 1SF6 load break swithFRLN36-12D/125-31.5Set1
  XGN15-12 Inline SwitchgearSet1 2Operating mechanismElectric AC2200Set1
1SF6 load break swithFLN36-12/620-20Set1 3Gas meter Set1
2Operating mechanismManual A typeSet1 4Outline Electromagnetic lock375#Set1
3Gas meter Set1 5Lighting ArresterHY5WS 17/50Set1
4Interlock for up and down door Set1 6SensorCG5-10 140mmSet1
5Lighting ArresterHY5WS 17/50Set1 7Voltage displayL-6Set1
6SensorCG5-10 140mmSet1 8Fuse10A-63ASet1
7Voltage displayDXN-QSet1 9Sheet metal375*1000*1635Set1
8Electromagnetic lockDSN-Z 220VSet1     
9Sheet metal375*916*1635Set1 NO.NameSpecificationUnitQty
       XGN15-12 Inline VCB switchgearSet1
NO.NameSpecificationUnitQty 1VCBVS1-12/630A-25KASet1
  XGN15-12 Inline SwitchgearSet1 2Disconecting switchGN30-12/630-25KASet1
1SF6 load break swithFLN36-12/620-20Set1 3Metal plate mechanism Set1
2Operating mechanismElectric AC2200Set1 4Lighting ArresterHY5WS 17/50Set1
3Gas meter Set1 5SensorCG5-10 140mmSet1
4Interlock for up and down door Set1 6Voltage displayDXN-QSet1
5Lighting ArresterHY5WS 17/50Set1 7Electromagnetic lockDSN-Z 220VSet1
6SensorCG5-10 140mmSet1 8Sheet metal750*916*1885Set1
7Voltage displayDXN-QSet1     
8Electromagnetic lockDSN-Z 220VSet1 NO.NameSpecificationUnitQty
9Sheet metal375*916*1635Set1   XGN17-12 Outline VCB switchgearSet1
     1VCBVS1-24/630A-25KASet1
NO.NameSpecificationUnitQty 2Disconecting switchGN30-10/630-25KASet1
  XGN15-12 Outline SwitchgearSet1 3Metal plate mechanism Set1
1SF6 load break swithFRLN36-12D/125-31.5Set1 4Lighting ArresterHY5WS 17/50Set1
2Operating mechanismManual A typeSet1 5SensorCG5-10 140mmSet1
3Gas meter Set1 6Voltage displayDXN-TSet1
4Outline Electromagnetic lock375#Set1 7Sheet metal1000*1210*2300Set1
5Lighting ArresterHY5WS 17/50Set1 8Grounding knifeJN15-12Set1
6SensorCG5-10 140mmSet1     
7Voltage displayL-6Set1 Note;This price without Copper bar,without current transformer,without seal plate. 
8Fuse10A-63ASet1  extra add 20 usd ,if the Sheet metal need higher one floor or wider one floor 
9Sheet metal375*1000*1635Set1      
 