Vd4-12kv/630A-25ka Vacuum Circuit Breaker Vcb Single Spring Cast Pole Chain Cocking Lever Insulated Cylinder Phase Distance 150mm Vcb

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 520 ~ 3800

Description
Product Description

1 Summarize
VS1 type indoor high voltage vacuum circuit breaker is one kind of three-phase AC 50Hz, rated voltage is 7.2-12 kv, indoor high voltage switch equipment. The circuit breaker meets the national standard of Chinese, GB1984-2003 <ac high-voltage circuit breaker>, JB 3855-1996 <3.6-40.5kv indoor high-voltage vacuum breaker>, DI403-91 < 10-35kv indoor high-voltage vacuum circuit breaker ordering technical conditions >and related IEC60694, IEC6227-100 standard requirements which with reliable interlocking function.
VS1 type indoor high voltage vacuum circuit breaker can be operated frequently, with the ability of multiple breaking and quick reclosing.
The VS1 type indoor high-voltage vacuum circuit breaker is designed with front and rear sub-assembly structure, which can be used for fixed installation cells as well as equipped with a separate hand cart with a chassis.  
 

Detailed Photos
 

 

Product Parameters
Rated Voltage12Kv
Rated Frequency50Hz
Rated lightning impulse test voltage/fracture75/85kV(peak)
Rated at 1 min, withstand voltage/fracture
  • 42/48kV(effective values)
  • Rated operating sequence
O-t-CO-t'-CO
ModelRated Current(kA)Rated short  circuit breaking current (kA)
  • Rated short close current KA(Peak)kA
  • Rated duration time  of short-circuit S
  • Breaking times
  • Mechanical lifetime
VS1-12630
1250
20/2550/63
 
4
 
10010000
 1250
1600
2000
2500
31.58045010000
 1250
1600
2000
2500
3150
4010043010000

Note: 20 kA, 25 kA, 31.5 kA, t= 0.3S, t'=180S
40kA  t=180S   t'=180S
b) Mechanical characteristics of circuit breaker
 
ModelItemsUnitData
1Contact distancemm11±1
2Overtravel3.5±0.5
3The characteric of three phase opening and closing at different period   ms≤2
4Closing contact jumping timeMs≤2
5Closing contact contact pressureN20kA25 kA31.4 kA40 kA
   2000±  2002400 ±2003100±  2004750±   250
6Average Closing speedm/s0.9-1.2
7Average Opening speed 05-0.8

c) Opening and Closing action time
Closing   time                     ≤100ms
Opening  time                     ≤50ms
Arcing   time                      ≤15ms
Breaking  time                     ≤65ms

1.2.2 Technical data for trip and interlock electromagnet 
ItemPower  VA 
Opening trip     TQ368
220/110
Closing trip      HQ368
Interlock trip     Y14.8
Overcurrent trip   7(Y8 Y9)--

1.2.3 Technical data for motor operation mechanism
 
Rated Voltage VPower WStorage time SApplicable current Level kA
220/11070≤1020 25 31.5
220/110100≤1040


 
Certifications

Packaging & Shipping

Company Profile

Our Advantages

 

After Sales Service

 

Product Tag:
Related categories:
Scroll to Top