Description
Automatic capacitance inductance tester (XHCL910)In order to reduce the reactive power loss, the power system usually uses a parallel capacitor bank method to improve the power factor.
In practical applications, the accident compensation rate of the capacitor compensation device is relatively high, which is determined by the characteristics of the working state of the capacitor device. Therefore, it is very important to check the capacitor device regularly and find capacitor defects early to avoid the expansion of the fault.
In the field, the capacitors are connected in parallel in groups, so the general capacitance meter needs to be removed after the lead wires are removed, the workload is large, and the wiring errors are easily caused.
To this end, the newly developed capacitor and inductance tester of our company measures a single capacitor of a group of parallel capacitors without disconnecting the wire, and can also measure the inductance and current; the wiring is convenient, the operation is simple, and the workload of the maintenance personnel is reduced.
The test efficiency of the site is greatly improved, and the safety guarantee for the normal operation of the power grid is provided.
The instrument can measure a single capacitor of a group of parallel capacitors without disconnecting the line, which is convenient to test.
It can also display the measured voltage, current, loss, capacity, frequency, impedance and other data while measuring the capacitance value;
The instrument displays the measured inductance value and also displays the measured voltage, current, loss, capacity, frequency, impedance and other data;
The instrument displays the measured current value and also displays the data such as the frequency of the current;
In addition to measuring the group of capacitors, the instrument can also measure △ type, Y type connection capacitors, etc.;
The instrument adopts 320×240 large-screen liquid crystal display, Chinese menu prompts, easy to operate;
The instrument has built-in large-capacity non-volatile memory: each test option can store 256 sets of data;
Built-in USB flash drive controller interface: can export instrument memory data for easy report generation;
The instrument has built-in high-precision real-time clock function: date and time calibration is possible;
The instrument comes with a high-speed micro thermal printer: printable measurement and historical data;
Instrument test power supply overcurrent protection function: Test the power supply output short circuit will not damage the instrument.
Main Specifications
Measuring range Capacitance: 2uF ~ 2000uF
Inductance: 5mH ~ 5000mH
Current: 20mA~2000mA
Measurement accuracy Capacitance: ± (1% reading + 2 words)
Inductance: ± (1% reading + 5 words)
Current: ± (1% reading + 2 words)
Dimensions 345mm × 295mm × 175mm
Instrument weight 7kg
All interfaces will be made and displayed in English after your orderPackaging: Wooden case filled with foam
Shipping: by Air, Sea, Express, etc.
Shipping time: 7-15 days if it's in stock.