HVHIPOT Customized GDCL series 10kA Impulse Current Generator for Zinc Oxide Arrester

Min.Order: 1
Product origin: Wuhan, Hubei, China
Infringement complaint: complaintComplaint
US$ 38000 ~ 53000

Description
customized GDCL series 10kA Impulse Current Generator for zinc oxide arrester

I.
 
General information


GDCL-10kA Impulse Current Test System is mainly used for the current flow capacity test of zinc oxide arrester in high voltage power distribution system, to generate lightning impulse current (8/20μs, etc.) Test and verification of residual voltage value, or used for other scientific research experiments.

II. Use Condition
 
  1. Altitude: 1000M;
  2. Ambient temperature: -10ºC~+40ºC, maximum daily temperature difference: 25ºC;
  3. Relative humidity: 85% (20ºC) without condensation;
  4. Service environment: Indoor;
  5. No conductive dust, no fire and explosion hazards, no corrosive metal and insulating Gases;
  6. Ground cable should be as short and thick as possible, and the loop should be grounded at one point.


III. Applied Standard
 
  1. GB/T 18802.12-2014 Low-voltage surge protective devices-Part 12: Surge protective devices connected to low-voltage power distribution systems-Selection and application principles
  2. GB/T 16927.1-2011 High-voltage test techniques -Part 1: General definitions and test requirements
  3. GB/T 16927.2-2013 High-voltage test techniques -Part 2:  Measuring systems
  4. GB/T 17626.5-2019 Electromagnetic compatibility-Testing and measurement techniques-Surge immunity test
  5. IEC61000-4-5  Electromagnetic compatibility (EMC)  Part 4-5: Testing and measurement techniques - Surge immunity test
  6. IEC61643.11: Low-voltage surge protective devices Part 11: Surge protective devices connected to low-voltage power systems-Requirements and test methods
  7. IEC61643-21: Low voltage surge protective devices (SPD) Part 21: Surge protective devices connected to telecommunications and signaling networks-Performance requirements and testing methods


IV. Technical Specifications
The main technical parameters of the test platform are:
 
  1. Nominal voltage: 150kV
  2. Rated voltage: 75kV
  3. Rated energy: 22.5kJ
  4. Impulse capacitance: 90k/4uF*2 units, two in series and in parallel.
  5. The total number of stages: 1
  6. Output waveform: 8/20 waveform 10kA
  7. Rated capacitance: 4uF/90kV
  8. The impulse current waveform parameters and their deviations meet the requirements of GB/T 311.1 and GB/T 16927.1 national standards.
  9. Minimum output voltage: ≥±10% rated voltage
  10. Charging voltage instability: <±1.0%
  11. Duration of use: above 2/3 of the rated voltage, it can be continuously operated by charging and discharging every 120 seconds; below 2/3 of the rated voltage, it can be continuously operated by charging and discharging once every 60 seconds.


Product Tag: