2MW Economic Natural Gas Generator

Min.Order: 1
Product origin: Jinan, Shandong, China
Infringement complaint: complaintComplaint
US$ 108680 ~ 148680

Description
500kw 700kw 1mw 2mw 4mw 5mw 2MW economic Natural Gas Generator

Jichai Brand Generator is designed and manufactured to be high quality, long usage life, easy operation, low maintenance cost, high intelligence with low engine speed, low fuel consumption, low gas quality requirement, tough environmental adaptability, high stability and low fluctuation. The generator is desirable for industrial power solution.
MAIN SPECIFICATIONS OF GAS GENERATOR SET
Model700GF-T Gas Engine ModelM12V190ZL
Rated power700kW/875KVA AlternatorSiemens Series
Rated voltage400 V Starting method24V DC electric start
Rated speed1000rpm Voltage regulationAutomatic
Rated frequency50Hz Cooling ModeClose type water cool
Rated current902A Heat Consumption£ 9800kJ/kWh
Power factor0.8 Lagging Dimension (mm)5120x2040x2219mm
Control modeElectric control Net Weight (kg)14500

MAIN ELECTRICAL PERFORMANCE OF THE GAS GENERATOR
Voltage
Stabilized regulationInstantaneous regulationRecovery timeFluctuation
±2.5%+20%2 S1%
Frequency
Stabilized regulationInstantaneous regulationRecovery timeFluctuation
0-5% adjustable+10%,-12%< 10 S1%

MAIN SPECIFICATIONS OF GAS ENGINE
ModelM12V190ZL
Rated power700kW/875KVA
Number and layout of cylinders:12-cylinders, V-type, 60° included angle
TypeFour strokes, Closed type water cooled, Turbo-charged, Electronic ignition, Electronic speed governor
Ignition typeSpark plug ignition
Intake gas pressure required7-9kPa
Bore´Stroke190´210 mm
Speed Governor(Woodward) EGS-02 Electric governor
Oil consumption£ 0.6g/kWh
Total lubricating oil capacity (Liters)200L
Exhaust temperature (before turbine)£ 680 °C
Heavy overhauling period36,000h
MAIN SPECIFICATIONS OF ALTERNATOR
 
Alternator modelExciting modelInsulation classConnectionCoolingStructure type
1FC5456-6TA42 (SIEMENS)BrushlessClass F3-phase, 4-wireAir cooledAVR and reactive droop regulator assembled in alternator
 
(Kindly Noted: data shown in above table tested under standard working condition: 25 Dec C, atmospheric pressure 100kPa, relative humidity 30%, altitude <1000m.)

Requirments for natural gas
1.Methane should be at least 95%
2.The natural gas temperature should be between 0-60 ºC
3. No inpurity should be in the gas. Water in the gas should be less than 20g/Nm3.
4. Heat value should be at least 8500kcal/m3, if less than this value, the power of the engine will be declined.
5. Gas pressure should be 3-100KPa, if the pressure is less than 3KPa, booster fan is necessary.
6.The gas should be dehydrated and desulfurated. Make sure that there is no liquid in the gas. H2S<200mg/Nm3


CONTROL PANEL
Control panel is panel type, vertical structure, model is GPL700. Control panel is equipped with meters showing various parameters of operating status, automatic air switch and timer. All of the electric cells possess three-proof functions.

The Generator possesses the following automatic monitoring and protective functions:

A) Audio or visual alarm for:
-   High oil and water temperature
-   Low oil pressure
-   Over current
-   Short circuit
-   Over-speed
-   Reverse power
B) Shut-off for:
-   Low oil pressure
-   Over-speed
-   Short circuit
-   Over-speed
-   Reverse power
C) Trip-off for:
-  Over-current
-  Short circuit
-  Reverse power
The generator can not only supply power directly to load but also can be paralleled running.

OPTIONAL DEVICE
Steel Soundproof Container (sound attenuated canopy)

CHP/ Cogeneration/CCHP Trigeneration
ATS and Synchronization Parallelling Panel
Oil and Water Heater
Product Tag:
Related categories:
Scroll to Top