Eaton 93pr UPS (uninterruptible power system) 25-200 Kw Modular UPS

Min.Order: 1
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ 5216 ~ 24166

Description

Eaton 93PR UPS

 

Eaton 93PR UPS is a world-class modular, scalable and hot swappable UPS. Lowest total cost of ownership and maximum availability - taking scalability, resiliency, safety and efficiency to the next level. Industry-leading efficiency exceeds 96% in double conversion mode and reaches top 99% with Eaton's ESS technology. Together with world-class intelligent software solutions for monitoring and management, Eaton 93PR is the surest way to secure the continuity of your mission critical applications.
 

Eaton 93PR UPS Technical Specifications

General
UPS output power rating (1.0 p.f.)25, 50, 75, 100, 125, 150, 175, 200kW
Efficiency in double conversion mode> 96%
Efficiency in Energy Saver System (ESS)> 99%
Static bypass rating200kW
External parallelingup to 4 units with HotSync technology
UPS topologyDouble conversion
UPS degree of protectionIP20
Acoustic noise at 1 m, in 25 °C ambient temperature< 70 dBA in double conversion
< 55 dBA in ESS
Altitude (max)1000m above sea level at 40 °C. Maximum 2000m with 1% derating per each add. 100 m
Input
Rated input voltage220/380 V, 230/400 V, 240/415 V 50/60 Hz
Voltage tolerance - Rectifier input187 to 276 V
Voltage tolerance - Bypass inputrated voltage -15% / +10%
Rated input frequency
Frequency tolerance
50 or 60 Hz, user configurable
40 to 72 Hz
Input wiring3 phase + neutral
Input power factor at 100% load> 0.99
Input ITHD< 3%
Rated input r.m.s current25kW50kW75kW100kW125kW150kW175kW200kW
380V40 A80 A120 A159 A199 A239 A278 A318 A
400V38 A76 A114 A151 A189 A227 A264 A302 A
415V37 A73 A110 A146 A182 A219 A255 A291 A
Soft start capabilityYes
Internal backfeed protectionYes
Output
Output wiring3 phase + neutral
Rated output voltage rating220/380 V, 230/400 V, 240/415 V, configurable
Total voltage harmonic distortion< 1% (100% linear load); < 3% (100% non-linear load)
Output power factor1.0
Permitted load power factor0,8 lagging - 0,8 leading
Overload on inverter10 min 102-110%; 60 sec 111-125%; 10 sec 126-150%; 300 ms > 150%.
Overload on bypassContinuous < 125%, 20 ms 1000%
Battery
Battery type12V, VRLA
Charging methodABM technology or Float
Temperature compensationOptional
Battery nominal voltage (VRLA)480 V
Battery quantity36 to 44 blocks. Default is 40 blocks
Charge current limitDefault 5A, configurable maximum 25A per UPM
Battery start capabilityYes
Communications
Minislot3 communication bays
Network/SNMP interfaceYes, optional
Serial portsBuilt-in host and device USB
Standard connectivity portsMini-slot ports for optional cards, Device USB and Host USB, RS-232 service port, relay output, 5 building alarm inputs and a dedicated EPO, Web and SNMP card
Accessories
 MiniSlot connectivity (Web/SNMP, ModBus/Jbus, Relay)
External Battery Cabinet(EBC)
Parallel Tie Cabinet(PTC)
External Maintenance Bypass Switches(EMBS)
External Battery Cabinet Breaker(EBCB)
Compliance with standards
SafetyIEC 62040-1
EMCIEC 62040-2
PerformanceIEC 62040-3
Mechanical
Weight without UPM368kg nett
25kW UPM Weight28kg nett
UPS dimension (W x D x H)603 x 1013 x 2050 mm